ELECTRICAL CONNECTIONS
•
It is advisable to make all connections with flexible electric wire.
•
The power lines must be distanced from the hot parts.
•
The burner installation is allowed only in environments with
pollution degree 2 as indicated in annex M of the EN 60335-
1:2008-07 regulation.
•
Make sure that the power line to which the unit will be connected,
has frequency and voltage values suitable for the burner.
•
The three-phase or single-phase power supply line must have
a switch with fuses. The standards also require a switch on the
burner's power line located outside the boiler room where it can be
accessed easily.
•
The main line, the relevant switch with fuses and the possible
limiter must be suitable to support the maximum current absorbed
by the burner.
•
For the mains supply connection is required an omnipolar switch
with a contact opening gap equal or above 3 mm in accordance
with current safety regulations.
•
Refer to the wiring diagram for electrical connections (line and
thermostats).
•
Remove the external insulating seal of the supply pipe necessary
for the connection, preventing the cable to touch metal parts.
CAUTION / WARNINGS
Only professionally qualified personnel may open the burner
electrical switchboard.
The electric motor is equipped with an automatic reset thermal cut-
out that causes it to stop when overheating.
CAUTION / WARNINGS
If it stops please make sure that the motor is in good conditions
and verify the causes of its overheating.