TECHNICAL FUNCTIONAL CHARACTERISTICS
• Operation with two progressive power stages.
•
Possibility to obtain great combustion values through combu-
stion air and combustion head regulation.
•
Ability to operate with output modulation by means of automatic
regulator mounted on the control panel (to be ordered separa-
tely with the modulation kit).
•
Easy maintenance as the mixing unit can be removed without
having to disassemble the burner from the boiler.
• Valve seal control according to European Standard EN 676.
•
Gas train complete with check valve, operating and safety val-
ve, valve seal control, minimum pressure switch, pressure re
-
gulator and gas filter.
•
Flame detection by means of ionisation electrode.
DESIGN CHARACTERISTICS
•
Sliding generator connection flange to adapt the head protru-
sion to the various types of heat generators.
•
Hinge opening on both sides for easy access to the combustion
head when burner is installed.
•
7-pole connector for the auxiliary power supply and thermostat
connection, 4-pole connector for the connection to the electro-
nic power regulator.
•
Three-phase electric motor to run fan.
• Electric system with protection class IP54.
•
Display showing the operating sequence and error code in the
event of a lockout.
•
Gas fuel flow regulation through servomotor that controls the
throttle.
• Flame inspection glass.
• Air damper closing in pause to prevent any heat dispersion to
the flue through air regulation servomotor.
•
Gas train outlet from above.
OPERATING RANGE
kW
40
80
120
160
200
400
240
280
320
kcal/hx10.000
2.5
5
7.5
10
0
12.5
15
17.5
20
800 1200 1600 2000 2400 2800 3200 3600
40
80
120
160
200
240
280
320
360
10 20 30 40 50 60 70 80 90 100 110 120 130 140
360
4000
400
160 180
400
4400
440
200 220
mbar
0002922930
Stm³/h (G.P.L.)
Stm³/h (Metano)
BGN 300..
BGN 350..
IMPORTANT
The operating ranges are obtained from test boilers corresponding to Standard EN676 and are indicative of the burner-boiler com-
bination. For correct working of the burner the size of the combustion chamber must correspond to current regulations; if not the
manufacturers must be consulted.
The burner should not work outside the indicated work range.
Summary of Contents for BGN 300 DSPGN ME
Page 2: ......
Page 28: ...ITALIANO 26 30 0006160204_201508 SCHEMI ELETTRICI ...
Page 29: ...ITALIANO 27 30 0006160204_201508 ...
Page 30: ...ITALIANO 28 30 0006160204_201508 BT1 BA BP I1 I2 I3 I4 ...
Page 32: ...ITALIANO 30 30 0006160204_201508 ...
Page 58: ...ENGLISH 26 30 0006160204_201508 WIRING DIAGRAMS ...
Page 59: ...ENGLISH 27 30 0006160204_201508 ...
Page 60: ...ENGLISH 28 30 0006160204_201508 BT1 BA BP I1 I2 I3 I4 ...
Page 62: ...ENGLISH 30 30 0006160204_201508 ...
Page 63: ......