AIR REGULATION ON COMBUSTION HEAD  

(See dr. n°  0002933310)

I

Warning: 

When, as in this case, the burner is provided with gas valves 

model MB-VEF.., DMV-VEF.., by moving the air regulation 

device on the combustion head there automatically and 

unavoidably occurs a gas output variation (see chapter Valve 

operation principle, model MB-VEF.., DMV-VEF..).

The combustion head is equipped with a regulation device, so as to 

open or close the air passage between disk and head. By closing 

the passage, it is thus possible to obtain a high pressure upstream 

of the disk also for low flow rates. The high air speed and turbulence 

allows a better penetration of the same into the fuel and therefore, 

an excellent mixture and flame stability. It may be necessary to have 
a high air pressure upstream of the disk, so as to prevent flame 

pulses. This condition is indispensable when the burner operates 

on pressurised combustion chamber and/or with high heating load. 

From what said above it is evident that the device closing the air 

on the combustion head must be set to such position as to always 

obtain, behind the disk, a very high air pressure value. It is advisable 

to regulate so as to have such air closure on the head as to require 

the  opening  of  the  air  damper  regulating  the  flow  of  the  burner 

ventilator suction. Of course, this condition must only occur when 

the burner is operating at the maximum desired output. In practice, 

the regulation must start with the device that closes the air on the 

combustion head in an intermediate position, igniting the burner for 

an indicative regulation as explained above.

When the maximum desired output is reached, correct the position 

of the device closing the air on the combustion head by moving it 

forwards or backwards so as to have a suitable air flow for the output, 

with suction air regulation damper sensibly open 
(see dr. n° 0002933310).

!

To facilitate the combustion head regulation, see table (dr. 

n° 0002933200)

When reducing the air passage on the combustion head, avoid 

closing it completely, which may cause an excessive heating of 

the head with a consequent quick deterioration. Perfectly adjust to 

central position with respect to the disk. Note that if not perfectly 

centred with respect to the disk may cause a wrong combustion and 

an excessive head heating, with a consequent quick deterioration. 

The check is carried out by looking through the inspection hole on 

the rear side of the burner. Afterwards, tighten the screws locking the 

position of the air regulation device on the combustion head.

!

Check that ignition is regular because if the controller 

has been moved forward, the output air speed could be 

so  high  as  to  make  ignition  difficult.  In  such  a  case,  it  is 

necessary to move backwards, degree by degree, the 

regulator until reaching the position in which the igni-

tion  is  regular  and  accept  this  new  position  as  definitive. 
We still remind you that it is preferable, for the small flame, 

to limit the air quantity to the minimum indispensable to have 

a safe ignition even in the most demanding case.

The minimum ionisation current for the control box to run is 6 

µA. The burner flame generates a markedly higher current that 

will not normally require any control box checks.

If you want to measure the ionisation current you have to con

-

nect a milliammeter in series to the ionisation electrode cable, 

opening connector “C” (see diagram).

Summary of Contents for BGN 200 LX

Page 1: ...ale istallazione impiego manutenzione BGN 200 LX LX V BGN 300 LX LX V BGN 390 LX LX V BGN 540 LX LX V Maintenance use and installation manual Manual de mantenimiento uso e instalaci n Manuel d install...

Page 2: ......

Page 3: ...ommencer utilise le br leur lire attentivement les recommandations de la notice RECOMMANDATIONS A L ATTENTION DE L UTILISATEUR POUR UN USAGE DU BRULEUR EN TOUTE SECURITE jointe au manuel d in structio...

Page 4: ...0006081062_200904...

Page 5: ...correggere se necessario il rapporto tarato agendo sulla vite V fino a quando il valore misurato ottimale NOTA Per diminuire la quantit di aria rispetto al gas e quindi per aumentare la percentuale d...

Page 6: ...ion atmosfere V min mini max maxi N 1 mbar pL max maxi 100 mbar V max maxi 3 1 pF max maxi 5 mbar pBr max maxi 100 mbar pL min mini 0 4 mbar pBr min mini 0 5 mbar pF min mini 2 mbar V min mini 0 75 1...

Page 7: ...e 9 Sostituirla 10 Se la massa dell apparecchiatura non efficiente non si verifica la corrente di ionizzazione Verificare l efficienza della massa all apposito morsetto della apparecchiatura e al coll...

Page 8: ...36 36 0006081062_200904 I T A L I A N O...

Page 9: ...eclare under our own responsibility that our CE marked products Series Sparkgas BTG BGN Minicomist Comist RiNOx BT BTL GI GI Mist PYR TS TBG Description domestic and industrial blown air burners fired...

Page 10: ...r or if the owner moves and leaves the equipment make sure that the booklet always goes with the equipment so it can be consulted by the new owner and or installer For all equipment with optionals or...

Page 11: ...rent law and regulations since incorrect installation may cause damage to person animals or things for which damage the manufacturer shall not can be held responsible Before installation it is advisab...

Page 12: ...N 4 M12 N 4 M20 N 4 M20 N 6 M20 EXAGONAL NUTS N 4 M12 N 4 M20 N 4 M20 N 6 M20 FLAT WASHERS N 4 M12 N 4 M20 N 4 M20 N 6 20 BGN 200 LX V BGN 300 LX V BGN 390 LX V BGN 540 LX V THERMIC CAPACITY MAX kW 21...

Page 13: ...Control box MOD A A1 A2 B1 B5 C D MIN D MAX E F BGN 200 LX 835 400 435 580 150 1630 280 480 300 220 BGN 300 LX 880 400 480 580 177 1630 280 480 316 275 BGN 390 LX 880 400 480 580 177 1630 280 480 316...

Page 14: ...regulation servomotor 5 Hinge 6 Combustion head air control knob 7 Fan motor 8 Air pressure switch 9 Control box MOD A A1 A2 B1 B5 C D MIN D MAX E F BGN 540 LX 1155 470 685 695 283 2110 330 600 400 35...

Page 15: ...V 10 1 Frequency converter BGN 300 390 LX V MOD A A1 A2 B1 B5 C D MIN D MAX E F BGN 200 LX V 835 400 435 580 150 1630 280 480 300 220 BGN 300 LX V 880 400 480 580 177 1870 280 480 316 275 BGN 390 LX...

Page 16: ...rvomotor 5 Hinge 6 Combustion head air control knob 7 Fan motor 8 Air pressure switch 9 Control box 10 Frequency converter MOD A A1 A2 B1 B5 C D MIN D MAX E F BGN 540 LX V 1155 470 685 695 283 2165 33...

Page 17: ...3 5 7 9 11 13 15 Campo di lavoro Operating field Arbeitsfeld BGN 200 LX X 8 40 mm Potenzialit Power Kapazit t kW Position of air diffusor X min left and X max right BGN 200LX Operating field BGN 200LX...

Page 18: ...7 Campo di lavoro Operating field Arbeitsfeld BGN 300 LX X 10 40 mm Potenzialit Power Kapazit t kW Position of air diffusor X min left and X max right BGN 300LX Operating field BGN 300LX X 10 40mm Kw...

Page 19: ...9 11 13 15 17 Operating field BGN 390 LX X 10 40 mm PFeu power kW pFR combustion pressure mbar Position of air diffusor X min left and X max right BGN 390LX Operating field BGN 300LX X 10 40mm Kw Pow...

Page 20: ...TING FIELD i The working fields are obtained from test boilers corresponding to the standard EN676 and are indicatively for the combination burner boiler For correct working of the burner the size of...

Page 21: ...adjusted while working at the maximum capacity actually used by the burner The delivery pressure must be adjusted to a figure slightly lower than the maximum obtainable that which is obtained when the...

Page 22: ...ion chamber Burner flange Pressure detection pipe connection nipple in combustion chamber Pressure take off in combustion chambe CHAMBER FOR MODEL BGN 540 LX FOR MODELS BGN 200 LX BGN390 LX N 00029349...

Page 23: ...3 Turn the cam 6 so that the float exerts sufficient pressure on the two cables then tighten the screws that fasten the cable float Finally connect the two 7 and 4 pole plugs the housings for the cabl...

Page 24: ...tic valve allows the gas supply to increase to its set maximum If there is no flame the control box stops in its safety lock out LED 7 within 3 seconds from the opening of the main valve In the case o...

Page 25: ...VEF DMV VEF set the desired value see the specific instruc tions for the gas valve MB VEF DMV VEF in the following pages 9 With the burner panel switch set to 0 and main circuit breaker on manually tu...

Page 26: ...singthecontact anormallyopencontact when air pressure in the burner reach a sufficient value Note that if the normally open contact does not close insufficient air pressure thecontrolboxperformsitscyc...

Page 27: ...regulation as explained above When the maximum desired output is reached correct the position of the device closing the air on the combustion head by moving it forwards or backwards so as to have a s...

Page 28: ...CT ADJUSTMENT Burner s head adjusting and xing knob Combustion air inlet Gate sensibly open MAINTENANCE The burner does not need special maintenance However it is advis able to check that the gas lter...

Page 29: ...iagram relative to the speci c burner model NOTE if the distance X is reduced the NOx emissions value falls Always adjust the distance X between the minimum and maximum valuesspeci ed in the work eld...

Page 30: ...22 36 0006081062_200904 E N G L I S H...

Page 31: ...23 36 0006081062_200904 E N G L I S H CAMS REGULATION SERVONMOTOR SQM 10 20 FOR BGN LX N 0002933490...

Page 32: ...nd of the tolerated post combustion period The tests will end only at the end of the pre ventilation time of the next start up The validity of working of the ame control circuit is checked each time t...

Page 33: ...mutation contact for air damper MIN position M Motor fan or burner NTC NTC resistor QRA UV probe R Thermostat or pressure probe RV Fuel valve with continuous regulation S Fuse SA Air damper servomotor...

Page 34: ...inal 19 12 t5 Time between end of t4 and consensus at power regu lator or at valve on terminal 20 18 t6 Post ventilation time with M2 3 t7 Time between consensus for start up and voltage at terminal 7...

Page 35: ...ltration of condensate into the command and control equipment Electromagnetic discharges must be checked on the applica tion plan Control program in the event of stopping indicating position of stop A...

Page 36: ...or pL blower pressure 9 Setting screw ratio V 10 Test point connection G 1 8 down stream of filter possible of both sides 11 Test point connection M4 down stream of V2 12 Setting screw zero point adju...

Page 37: ...29 36 0006081062_200904 E N G L I S H Pe Gas inlet pressure...

Page 38: ...30 36 0006081062_200904 E N G L I S H DUNGS mod DMV VEF 5065 11 5125 11 N 0006080717 Rev 2002 06 INSTRUCTIONS FOR DOUBLE SOLENOID VALVE GAS AIR RATIO CONTROL...

Page 39: ...31 36 0006081062_200904 E N G L I S H...

Page 40: ...N hacia los valores negativos Ponga el quemador al m ximo de la modula ci n mida el contenido de CO2 o O2 y CO en los humos y si fuera necesario ajuste la relaci n tarada con el tornillo V hasta que...

Page 41: ...pBr max maxi 100 mbar pL min mini 0 4 mbar pBr min mini 0 5 mbar pF min mini 2 mbar V min mini 0 75 1 V pBr pL MB VEF Einstellbereich Setting range Plange de r glage Campo di regolazione Correcci n pu...

Page 42: ...os 8 Limpiar 9 Sustituirlo 10 Si la puesta a tierra del quemador no funciona la corriente de ionizaci n no se efect a Controlar la puesta a tierra del borne del aparato y del sistema el ctrico Llama a...

Page 43: ...36 36 0006081062_200904 E S P A O L...

Page 44: ...149 162 0006081062_200904...

Page 45: ...150 162 0006081062_200904...

Page 46: ...151 162 0006081062_200904...

Page 47: ...152 162 0006081062_200904...

Page 48: ...153 162 0006081062_200904...

Page 49: ...154 162 0006081062_200904...

Page 50: ...155 162 0006081062_200904...

Page 51: ...156 162 0006081062_200904...

Page 52: ...157 162 0006081062_200904...

Page 53: ...158 162 0006081062_200904...

Reviews: