ENGLISH
18 / 34
0006160161_201711
During normal operation, the modulation probe installed on the
boiler measures any variation demands and automatically adjusts
the fuel and combustion air flow rate by starting the air/gas flow rate
modulation servomotors, modulating the output.
This causes the air/gas output control system to balance the amount
of heat supplied to the boiler with the amount it gives off during use.
If a flame does not appear within three seconds from the opening of
the gas valves, the control equipment will lockout (shutting down the
boiler completely and showing the corresponding error message on
the display).
To "unlock" the equipment, press the RESET button for about half a
second.
DETAIL OF BUTTERFLY VALVE FOR GAS FLOW REGULATION
BY MEANS OF SERVO MOTOR
A) Butterfly gas valve position reference index
B) Gas modulation servomotor
Summary of Contents for 17350010
Page 2: ......
Page 32: ...ITALIANO 30 34 0006160161_201711 SCHEMI ELETTRICI...
Page 33: ...ITALIANO 31 34 0006160161_201711...
Page 34: ...ITALIANO 32 34 0006160161_201711...
Page 36: ......
Page 66: ...ENGLISH 30 34 0006160161_201711 WIRING DIAGRAMS...
Page 67: ...ENGLISH 31 34 0006160161_201711...
Page 68: ...ENGLISH 32 34 0006160161_201711...
Page 70: ......
Page 71: ......