Alternator #1 Temperature Threshold.
Controls the setpoint at which point field current is
reduced when the the alternator temperature sensor indicates an over-temp condition at the alter-
nator. Requires temperature sensor installation. Preset at 108
˚
.
Absorption Voltage.
Controls the maximum limit of allowable bulk voltage. Starts at value set
by battery program currently in use. Adjustment spans from 13.5 to 14.8 volts. To reverse direction
of scroll, release magnet and wait for LED to display Av code. Re-activate switch with magnet and
release when desired value is indicated.
Float Voltage.
Controls the maximum limit of allowable float voltage. Starts at value set by bat-
tery program currently in use. Adjustment spans from 13.0 to 13.8 volts. To reverse direction of
scroll, release magnet and wait for LED to display Fv code. Re-activate switch with magnet and
release when desired value is indicated.
Absorption Time.
Controls the minimum time period for non-calculated absorption charging.
Standard value set by battery program selected. Adjustment spans in tenths of hours from 12
minutes to six hours. To reverse direction of scroll, release magnet and wait for LED to display a1c
code. Re-activate switch with magnet and release when desired value is indicated.
Float Time.
Controls the minimum time period for non-calculated float charging. Standard value
set by battery program selected. Adjustment spans in tenths of hours from 12 minutes to six hours.
To reverse direction of scroll, release magnet and wait for LED to display F1c code. Re-activate
switch with magnet and release when desired value is indicated.
Field Threshold - Float To Absorption .
Controls the criteria the regulator uses to deter-
mine how hard the alternator has to be working to stay in calculated absorption charging mode.
Factory set at 67% field output. Raising “ffl” shortens “ffl” increases calculated absorption charge
time. Adjusted in 1% increments. Span of adjustment is 16% to 96%. To reverse direction of scroll,
release “ffl” code. Reactivate switch with magnet and release when desired value is indicated.
Field Threshold - Bulk To Absorption .
Controls the criteria the regulator uses to determine
how hard the alternator has to be working to stay in calculated bulk charging mode. Factory set
at 67% field output. Raising “fba” shortens calculated bulk charge time. Lower ing “fba” increases
calculated bulk charge time. Adjusted in 1% increments. Span of adjustment is 16% to 96%. To re-
verse direction of scroll, release magnet and wait for LED to display “fba” code. Re-activate switch
with magnet and release when desired value is indicated.
Slope Voltage Correction.
Adjusts the voltage (in milivolts) the regulator uses when moni-
toring battery temperature sensing. Can be custom adjusted to meet the needs of unique battery
technologies. Consult with battery manufacturer for specific slope voltage recommendations.
Battery #1 Temperature Threshold.
Controls the setpoint at which point field current is dis-
continued when the the battery temperature sensor indicates an over-temp condition at battery #1.
Requires temperature sensor installation. Preset at 52°C.
Default Program Settings By Battery Type
UFP
FDC
GEL
AGM
OPS
FSB
HAL
START DELAY (SECS.)
1
1
1
1
1
1
1
SOFT RAMP (SECS.)
60
60
60
60
60
60
60
BULK VOLTAGE
14.1
14.6
14.1
14.38
14.6
14.4
14.0
BULK TIME (MINIMUM)
30 MIN
30 MIN
30 MIN
30 MIN
30 MIN
30 MIN
30 MIN
ABSORPTION VOLTS
13.9
14.4
13.9
14.18
14.4
14.2
13.8
ABSORPTION TIME (MINIMUM)
30 MIN
30 MIN
30 MIN
30 MIN
30 MIN
30 MIN
30 MIN
FLOAT VOLTS
13.4
13.4
13.7
13.4
13.4
13.4
13.5
FLOAT TIME (MINIMUM)
30 MIN
30 MIN
30 MIN
30 MIN
30 MIN
30 MIN
30 MIN
FLOAT TIME (MAXIMUM)
6 HRS.
6 HRS.
6 HRS.
6 HRS.
6 HRS.
6 HRS.
6 HRS.
HIGH VOLTAGE ALARM (VOLTS)
15.2
15.6
15.1
15.38
15.6
15.4
15.0
LOW VOLTAGE ALARM (VOLTS)
12.5
12.5
12.5
12.5
12.5
12.5
12.5
MAX BAT. TEMP.
125˚F/52˚C
125˚F/52˚C
125˚F/52˚C
125˚F/52˚C
125˚F/52˚C
125˚F/52˚C
125˚F/52˚C
MAX ALT. TEMP.
225˚F/107˚C
225˚F/107˚C
225˚F/107˚C
225˚F/107˚C
225˚F/107˚C
225˚F/107˚C
225˚F/107˚C
- 12 -
Bulk Time.
Controls the minimum time period for non-calculated bulk charging. Standard value
set by battery program selected. Adjustment spans in tenths of hours from 12 minutes to six hours.
To reverse direction of scroll, release magnet and wait for LED to display b1c code. Re-activate
switch with magnet and release when desired value is indicated.