Advanced Programming

Accessing The Advanced Programming Mode

The MC-612-DUAL provides a broad range of advanced user adjustments in its password-protected Advanced Program 

mode. The Advanced Program mode is accessed via the Basic Program mode. To access the Advanced Program mode:
1.  With the regulator activated, TOUCH / HOLD the magnet to the RED dot on the regulator’s epoxy potting.
2.  The regulator will cycle to PRO. RELEASE the magnet from the switch.
3.  The  regulator will cycle through all of the Basic Program modes; bA, bEL, Ab2, and dSP -- followed by three dash-

es.

4.  TOUCH / HOLD when the three dashes are displayed. The dashes will be replaced by AP0 followed by AP1, and so 

on.

5.  When the display indicates AP5, RELEASE.
6.  The display will cycle to PrA, indicating entry into the Advanced Programming mode.

INDICATES ENTRY INTO PRO-

GRAM MODE
INDICATES SELECTION MODE 

FOR BATTERY TYPE
INDICATES SELECTION MODE 

FOR BELT LOAD MANAGER

INDICATES SELECTION MODE 

FOR BAT / ALT #2 TEMP SENSE
INDICATES SELECTION MODE 

FOR SHORT/ LONG DISPLAY
INDICATES END OF BASIC PRO-

GRAM MODE

INDICATES ENTRY INTO PASS-

WORD MODE FOR AP MODE
INDICATES PASSWORD FOR AD-

VANCED PROGRAM MODE
INDICATES ENTRY INTO THE AD-

VANCED PROGRAM MODE

Advanced Programming Modes

Making Advanced Programming Adjustments

Once accessed, the Advanced Program mode allows the user to adjust time, voltage and temperature settings for most 

operational modes. When the desired mode is indicated, TOUCH / HOLD the magnet to the RED dot on the epoxy pot-

ting. When the reed switch is engaged, the values for the various modes will scroll upward or downward. To reverse the 

direction of scroll:
1.  REMOVE the magnet from the reed switch.
2.  Wait for the mode indicator to be displayed.
3.  TOUCH / HOLD when the mode indicator is displayed. The values for that mode will begin to scroll in the opposite 

direction. Continue to HOLD until the desired value is displayed.

4.  REMOVE the magnet from the RED dot. The mode indicator will be displayed again, followed by the indicator for the 

next Advanced Programming mode.

The Advanced Programming Modes are as follows:

Start Delay.

 

Controls the amount of time from regulator activation to start of charging. Factory 

preset at onesecond. Can be adjusted to a maximum of 200 seconds. To reverse direction of scroll, 

release magnet and wait for LED to display dlc code. Re-activate switch with magnet and release 

when desired value is indicated.

Advanced Program Mode.

 

Once the correct password has been provided to unlock the Ad-

vanced  Program mode, the PrA display will be immediately followed by thirteen advanced control 

modes, including; start delay, compensation limit, bulk voltage and time, absorption voltage and 

time, float voltage and time, field thresholds, temperature limits and slope.

Compensation Limit.

 

Controls the maximum limit of allowable system voltage. Starts at value 

set by battery program currently in use. Adjustment spans from 14.1 to 15.9 volts. To reverse direc-

tion of scroll, release magnet and wait for LED to display Cl code. Re-activate switch with magnet 

and release when desired value is indicated.

High Voltage Limit.

 

Allows  user  adjustment  of  the  maximum  allowable  bulk  charging  volt-

age.  Can  be  set  to  a  maximum  level  of  15.6  volts,  enabling  functions  like  battery  equalization.  

WARNING: Extreme caution is required during any high voltage operation. Contact battery 

manufacturer for equalization/conditioning protocols for your battery type.

Bulk Voltage.

 

Controls the maximum limit of allowable bulk voltage. Starts at value set by battery 

program currently in use. Adjustment spans from 14.1 to 14.8 volts. To reverse direction of scroll, 

release magnet and wait for LED to display bv code. Re-activate switch with magnet and release 

when desired value is indicated.

- 11 -

Summary of Contents for MAX CHARGE MC-612-DUAL

Page 1: ...ternators are being used to charge the same large battery bank The MC 612 DUAL provides two field output connectors two power input connectors and two system ground connections making it pos sible to...

Page 2: ...rom inverters transmitters and other sources of RF noise convenient access and readability of the display The regulator wiring harness is 54 inches long providing a three to four foot radius for mount...

Page 3: ...BATTERY Temperature Sensor MC TS A Sensor lug connects to negative battery post enabling regula tor to monitor and respond to battery temperature condition USE CARE TO ENSURE POSITIVE AND NEGATIVE WI...

Page 4: ...switch or to the wire in the existing engine wiring loom that delivers switched voltage from the ignition switch In some cases an oil pressure switch may be used to activate the regulator In either ca...

Page 5: ...e 1 4 spade terminal from the terminal 12 pin Crimp the spade terminal to the sense wire and reconnect the spade to the 12 terminal pin Data TX and RX Terminals 13 and 14 Are currently for factory use...

Page 6: ...gramming features Included with the regulator is a small screwdriver that doubles as the regulator s programming tool A small magnet embedded in the tip of the screwdriver s handle allows the user to...

Page 7: ...ds the bulk charge time by an additional six minutes and compares real time to target values This will re occur until all values are met 5 Ramps down to Absorption voltage 6 Absorption Charge Regulato...

Page 8: ...code Indicates temperature setpoint for ambient alternator and battery temperatures Followed by degrees celsius Indicates in millivolts the voltage value used to control voltage compensation for batt...

Page 9: ...AgL Optima OPS as well as a factory default program UFP and a program for systems with voltage sensitive halogen equipment HAL Programming can be accomplished whenever the regulator is activated Syste...

Page 10: ...16 and 17 Programming For Secondary Alternator OR Regulator Temperature Sensor The regulator allows the user to select between the use or a second battery temperature sensor or a second alternator tem...

Page 11: ...ues for that mode will begin to scroll in the opposite direction Continue to HOLD until the desired value is displayed 4 REMOVE the magnet from the RED dot The mode indicator will be displayed again f...

Page 12: ...indicated Field Threshold Bulk To Absorption Controls the criteria the regulator uses to determine how hard the alternator has to be working to stay in calculated bulk charging mode Factory set at 67...

Page 13: ...at s capable of providing a signal to a user supplied and installed audible or visual alert to indicate the following while the regulator is in operation Small Engine Mode is activated Regulator is at...

Page 14: ...tery Sense wire and there is zero or an unexpected voltage reading at the BLUE wire contact our technical support staff at 360 435 6100 or e mail us at balmar balmar net If all voltages at the regulat...

Page 15: ...tery side of the isolator if an isolator is in use Use a SHIELDED alligator clip for post attachment Unintentional contact between the alligator clip and the alternator case could result in damage to...

Page 16: ...eplacement In order to expedite warranty claims more efficiently BALMAR asks that prior to returning a defective product for repair you call their customer service department for a warranty return aut...

Reviews: