IO-Link port parameter
Slot 2, Subslot 1
Index
Byte
Bit
Length
Contents
Values
Default
1
0
0
6 bits
Cycle time
0...63
0
0
6
2 bits
Cycle time base
0/1/2
0
2
0
0
1 byte
Data window offset
0...31
0
1
0
1 byte
Max. data input length
0...32
0
3
0
0
2 bits
Validation type
0...255
0
1
0
1 byte
Vendor ID byte0
0...255
0
2
0
1 byte
Vendor ID byte 1
0...255
0
3
0
1 byte
Vendor ID byte 2
0...255
0
4
0
1 byte
Device ID byte 0
0...255
0
5
0
1 byte
Device ID byte 1
0...255
0
6
0
16 bytes
Serial number
String
Empty string
4
0
0
1 bit
Parameter server upload
0/1
0
0
1
1 bit
Parameter server download
0/1
0
0
6
2 bits
Parameter server enable
0/1/2
0
5
0
0
1 byte
Process data length input
0...32
Fix per module
1
0
1 byte
Process data length output
0...32
Fix per module
Description of individual parameters
IO-Link diagnostics
This function can be used to permit / suppress all of the IO-Link module's diagnostics messages (visual diagnostics sig-
nals are unaffected).
IO-Link port function pin 4
Here the function of the IO-Link port can be defined:
Normally open
= Input as normally open contact
Normally closed
= Input as normally closed contact
Output
= Output function
IO-Link
= IO-Link function
Normally open after pa-
rameter configuration
= SIO mode; an IO-Link device can be configured via IO-Link and afterward switched
over to an SIO mode in which the IO-Link port pin functions as a simple normally open
switch input
Normally closed after pa-
rameter configuration
= SIO mode, as with normally open after configuration, but as normally closed switch
input
IO-Link port function pin 2
Here the function of the IO-Link port can be defined:
Normally open
= Input as normally open contact
Normally closed
= Input as normally closed contact
Output
= Output function
Diagnostics input
= Cable break detection
IO-Link safe state pin 4/2
This function is an extension of the IO-Link port starting configuration. A safe state that the port is to take on in the case
of a loss of bus communication can be predefined for the respective port.