6
Configuration via Explicit Messages
IO-Link Device
Parameteriza-
tion
There are two options for configuring an IO-Link device connected to the IO-Link port.
Configuration via the web server
refer to the "Web Server" chapter under "Device Properties"
Configuration via explicit messages
The following example describes how Rockwell RSLogix 5000 devices can be used to config-
ure an IO-Link device via
explicit messages.
For this purpose, the "MSG" components in the PLC program are used.
Read IO-Link
Parameter
Service Code
Class
Instance
Attribute
0x32
0x96
1-4 / 1-8 (corresponds to IO-Link port 1-4
for BNI EIP-502-105-R015 and IO-Link
ports 1-8 for BNI EIP-508-105-R015
0x03
(Read Parameter)
Source Length must correspond to at least the read parameters, but a larger value can also
be entered. (In this example, 100 bytes)
As the Source Element (Write) and as the Destination Element (Read),
create one SINT[100] array each and select the first line[0].