Balluff Inductive Coupler
Base BIC 1I0-I2A50-M30MI3-SM4A4A and
Remote BIC 2I0-I2A50-M30MI3-SM4A5A
www.balluff.com
11
8
IO-Link communication
8.2
Parameters
Various base parameters can be accessed via IO-Link. All parameters are read-only, so they
involve information, not configuration options. The "Identification data" can contain texts and
information about the base. The Direct Parameter page of the IO-Link device connected to
the remote is displayed in the "Parameter data".
DPP
SPDU
Description
Length
Default value
Index
Index
Sub
Index
Id
e
nti
fic
a
tio
n
da
ta
0 x 07
Vendor ID
2 bytes
0 x 0378
0 x 08
0 x 09
Device ID
3 bytes
0 x 050601
0 x 0A
0 x 0B
0 x 10
0
Vendor name
7 bytes
BALLUFF
0 x 11
0
Vendor text
15 bytes www.balluff.com
0 x 12
0
Product name
37 bytes
BIC 1I0-I2A50-M30MI3-
SM4A4A
0 x 13
0
Product ID
7 bytes
BIC000C
0 x 14
0
Product text
34 bytes BIC IOL Base
0 x 16
0
Hardware revision
3 bytes
0 x 17
0
Firmware revision
3 bytes
Pa
ram
e
te
ri
z
a
tio
n
da
ta
0 x 40
64
0
1
– 16
Direct Parameter page
of the IO-Link device
on the remote
16 bytes
8.3
Events
Event 1
Event 2
Event classification
Detailed information
Mode
Type
Instance
0 x F3
0 x 5112
0 x C0
0 x 30
0 x 03
0 x 5000
0 x 0100
0 x 0010
0 x 0002
coming
Error
Application
Hardware
Supply
Supply low
voltage
U2 = supply
+ 24 V
Supply voltage is too low
0 x B3
0 x 5112
0 x 80
0 x 30
0 x 03
0 x 5000
0 x 0100
0 x 0010
0 x 0002
going
Error
Application
Hardware
Supply
Supply low
voltage
U2 = supply
+ 24 V
Supply voltage is OK again