Instruction manual BES M18MF2-PSC80F-BV02-EXD

Instruction manual BES M18MF2-PSC80F-BV02-EXD

BA-S36036-GB-2018-20

BA-S36036-GB-2018-20

Page 1

Page 4

0102

Inductive Sensor

Order Code: BES05L3

BES M18MF2-PSC80F-BV02-EXD

Instruction manual

Balluff GmbH

Schurwaldstr. 9

D-73765 Neuhausen a.d.F.

Tel.  +49 7158 173-0

Fax. +49 7158 5010

www.balluff.com

[email protected]

Intended use

The inductive proximity switch is for use as contactless wearout-free limit switch in

industrial control systems.

It can be mounted inside gas-hazardous areas that require equipment of category 1G 

(zone 0) or dust-hazardous areas that require equipment of category 1G (zone 20).

If there are additional regulations for the particular design regarding the installation, they 

must be observed as well.

Safety instructions

•  Only professionals with sufficient knowledge are allowed to install and operate the device.

•   Prior to installation disconnect the system from power supply.

•   Comply with the provisions of the instruction manual.

•  Comply with the national regulations and installation provisions (e.g. EN 60079-14).

•   Absolutely abide by the specific conditions.

Installation and operation

•  Make sure that the device is used only in the area of application corresponding to its Ex marking.

•  Do not modify the device (e.g. painting).

•  Make sure that the housing of the proximity switch has electrical contact to a grounded metal structure.

•  Mount protection cap on housing finger tigth. Counter it with nut. (Protection cap and countering nut are in

  the scope of delivery).

•  Install cables according to the applicable regulations and protect them from damage.

•  The device complies with the EMC requirements for proximity switches according to

  EN 60947-5-2:2007+A1:2012.

•  Cables longer than 30 m can require additional EMC measures.

Maintenance, repairs and trouble-shooting

•  Do not modify or repair the device – its approval will expire. Contact the manufacturer for any problems.

•  Prevent dust from covering the device, i.e by regulary cleaning with a damp cloth.

•  Datasheet, EU type examination certificate and MTTF values are available on request.

•  Check safe mounting of the protection cap regularly.

•  Replace defective impact protection cap, check sensor for damage.

Specific conditions

•  Protect the device from UV light.

•  Markings that are not on the device will be found in the instruction manual.

•  Avoid electrostatic charge of plastic areas.

•  Connect the open cable endings outside the hazardous area or use a terminal box which is certified

  for hazardous areas.

•  Prevent the energy recovery trough terminal S.

•  The device is resistant against the risk of low mechanical danger of 4 J. Protect it from higher

  mechanical danger.

The following standards have been applied

:

EN 60079-0:2012 + A11:2013
EN 60079-18:2015
EN 60947-5-2:2007 + A1:2012
EN 50581:2012

IEC 60079-0: Edition 6.0 2011-06
IEC 60079-18: Edition 4.0 2014-12

Summary of Contents for BBES M18MF2-PSC80F-BV02-EXD

Page 1: ...deutsch Betriebsanleitung english User s guide fran ais Notice d utilisation espa ol Manual de instrucciones portugu s Manual de instru es BBES M18MF2 PSC80F BV02 EXD...

Page 2: ...x Ex II 1D Ex ma IIIC T90 C Da Baumusterpr fbescheinigung EPS 18 ATEX 1 015 X Benannte Stelle f r die berwachung des Qualit tssicherungssystems Physikalisch Technische Bundesanstalt PTB NB 0102 Bundes...

Page 3: ...umentation technique est archiv e par le fabricant IT La documentazione tecnica viene archiviata presso il costruttore ES El fabricante se encarga de archivar la documentaci n t cnica NL De technische...

Page 4: ...ter sichern Schlagschutzkappe und Kontermutter im Lieferumfang Anschlusskabel entsprechend den g ltigen Vorschriften verlegen und vor Besch digungen sch tzen Das Ger t erf llt die EMV Anforderungen f...

Page 5: ...mA DC Kurzschlussstrom des externen Stromkreises 100 A Elektrostatisch aufladbare Kunststoffoberfl chen Betrachtung nach Gruppe II Gas 472 mm Betrachtung nach Gruppe III Staub 1897 mm Geh usewerkstoff...

Page 6: ...zardous area gas or dust IGEX20a IGEX20Pa L S L BN BK BU 34 44 6 20 5 23 M18x1 2 5 24 LED betriebsm ig geerdeter metallischer Montagerahmen grounded metal frame Bauform type max Drehmoment max torque...

Page 7: ...churwaldstr 9 D 73765 Neuhausen a d F Tel 49 7158 173 0 Fax 49 7158 5010 www balluff com balluff balluff de Folgende Normen wurden angewandt EN 60079 0 2012 A11 2013 EN 60079 18 2015 EN 60947 5 2 2007...

Page 8: ...mity switch has electrical contact to a grounded metal structure Mount protection cap on housing finger tigth Counter it with nut Protection cap and countering nut are in the scope of delivery Install...

Page 9: ...ent 50 mA DC Short circuit current of external circuit 100 A Electrostatic chargeable plastic housing With reference to group II gas 472 mm With reference to group III dust 1897 mm Housing material Br...

Page 10: ...ous area gas or dust IGEX20a IGEX20Pa L S L BN BK BU 34 44 6 20 5 23 M18x1 2 5 24 LED betriebsm ig geerdeter metallischer Montagerahmen grounded metal frame Bauform type max Drehmoment max torque M12x...

Page 11: ...waldstr 9 D 73765 Neuhausen a d F Tel 49 7158 173 0 Fax 49 7158 5010 www balluff com balluff balluff de The following standards have been applied EN 60079 0 2012 A11 2013 EN 60079 18 2015 EN 60947 5 2...

Page 12: ...sur la douille filet e et le s curiser avec le contre crou Le capot de protection pare choc et le contre crou sont contenus dans la livraison Installer les c bles conform ment aux prescriptions appli...

Page 13: ...ant nominal 50 mA DC Courant de commutation 50 mA DC Courant de court circuit du circuit lectrique externe 100 A Surfaces en mati res synth tiques susceptibles d tre charg es d lectricit statique Cons...

Page 14: ...protection cap Dimensions Sch ma de raccordement Montage Code couleur BK noir BN brun BU bleu GY gris WH blanc Contenu de la livraison transport et limination V rifiez que l emballage et le contenu ne...

Page 15: ...waldstr 9 D 73765 Neuhausen a d F T l 49 7158 173 0 Fax 49 7158 5010 www balluff com balluff balluff de Les normes suivantes ont t appliqu es EN 60079 0 2012 A11 2013 EN 60079 18 2015 EN 60947 5 2 200...

Page 16: ...de protecci n y contratuerca incluidos en el volumen de suministro Coloque el cable de conexi n seg n las normas vigentes y prot jalo de posibles da os El dispositivo cumple los requisitos de compatib...

Page 17: ...superficie zona 21 90 C Tensi n nominal 27 V CC Tensi n de servicio 24 V CC 10 Corriente nominal 50 mA CC Corriente de conmutaci n 50 mA CC Cortocircuito del circuito externo 100 A Superficies pl stic...

Page 18: ...m 40 Nm Schlagschutzkappe Impact protection cap 0 Dimensiones Diagrama de conexiones Montaje C digo de color BK negro BN marr n BU azul GY gris WH blanco Volumen de suministro transporte y eliminaci n...

Page 19: ...Schurwaldstr 9 D 73765 Neuhausen a d F Tel 49 7158 173 0 Fax 49 7158 5010 www balluff com balluff balluff de Se han aplicado las siguientes normas EN 60079 0 2012 A11 2013 EN 60079 18 2015 EN 60947 5...

Page 20: ...contraporca A capa de prote o contra choque e a contraporca est o inclu das no material fornecido Instalar o cabo de conex o de acordo com as disposi es v lidas e proteger contra a poss veis danos O a...

Page 21: ...mente explosiva zona 21 20 C Ta 60 C Temperatura de superf cie zona 21 90 C Tens o de medi o 27 V DC Tens o operacional 24 V DC 10 Corrente de medi o 50 mA DC Tens o de comuta o 50 mA DC Corrente de c...

Page 22: ...Schlagschutzkappe Impact protection cap BES EXD Medidas Diagrama de liga o el trica Montagem C digo de cores BK preto BN marrom BU azul GY cinza WH branco Material fornecido transporte e elimina o Ver...

Page 23: ...Schurwaldstr 9 D 73765 Neuhausen a d F Tel 49 7158 173 0 Fax 49 7158 5010 www balluff com balluff balluff de Foram aplicadas as seguintes normas EN 60079 0 2012 A11 2013 EN 60079 18 2015 EN 60947 5 2...

Page 24: ...BES M18MF2 PSC80F BV02 EXD BA S36036 CHN 2018 20 1 0102 BES05L3 BES M18MF2 PSC80F BV02 EXD 1G 0 1D 20 EN 60079 14 EN 60947 5 2 2007 A1 2012 30m MTTF S 4 J...

Page 25: ...20 C Ta 60 C T5 0 20 C Ta 60 C T4 0 20 C Ta 60 C T3 0 20 C Ta 60 C T6 1 20 C Ta 60 C T5 1 20 C Ta 60 C T4 1 20 C Ta 60 C T3 1 20 C Ta 60 C 20 20 C Ta 60 C 20 90 C 21 20 C Ta 60 C 21 90 C 27 V DC 24 V...

Page 26: ...ardous area explosionsgef hrdeter Bereich Gas oder Staub hazardous area gas or dust IGEX20a IGEX20Pa L S L BN BK BU BES EXD betriebsm ig geerdeter metallischer Montagerahmen grounded metal frame Baufo...

Page 27: ...4 Balluff GmbH Schurwaldstr 9 D 73765 Neuhausen a d F 49 7158 173 0 49 7158 5010 www balluff com balluff balluff de EN 60079 0 2012 A11 2013 EN 60079 18 2015 EN 60947 5 2 2007 A1 2012 EN 50581 2012 I...

Page 28: ...BES M18MF2 PSC80F BV02 EXD BA S36036 RU 2018 20 1 0102 BES05L3 BES M18MF2 PSC80F BV02 EXD 1G 0 1D 20 EN 60079 14 EX EN 60947 5 2 2007 A1 2012 30 S 4 J...

Page 29: ...Ga Ex ma IIIC T90 C Da T6 0 20 C Ta 60 C T5 0 20 C Ta 60 C T4 0 20 C Ta 60 C T3 0 20 C Ta 60 C T6 1 20 C Ta 60 C T5 1 20 C Ta 60 C T4 1 20 C Ta 60 C T3 1 20 C Ta 60 C 20 20 C Ta 60 C 20 90 C 21 20 C...

Page 30: ...Bereich Gas oder Staub hazardous area gas or dust IGEX20a IGEX20Pa L S L BN BK BU 34 44 6 20 5 23 M18x1 2 5 24 LED betriebsm ig geerdeter metallischer Montagerahmen grounded metal frame Bauform type m...

Page 31: ...4 Balluff GmbH Schurwaldstr 9 D 73765 Neuhausen a d F 49 7158 173 0 49 7158 5010 www balluff com balluff balluff de EN 60079 0 2012 A11 2013 EN 60079 18 2015 EN 60947 5 2 2007 A1 2012 EN 50581 2012 I...

Page 32: ...e KY 41042 Phone 859 727 2200 Toll free 1 800 543 8390 Fax 859 727 4823 technicalsupport balluff com CN Service Center China Balluff Shanghai trading Co ltd Room 1006 Pujian Rd 145 Shanghai 200127 P R...