BIS C-602
Mounting Processor / Head
In order to set the PROFIBUS-DP address or to place the jumpers for the internal terminating
resistor, or to make the PROFIBUS-DP connections, the BIS C-602 processor must be
opened.
Take care that the device is unpowered. Loosen the 4 screws and remove the cover. Feed the
two remote bus cables through the cable clamps. See the following
for additional informa-
tion.
Opening the
Processor
BIS C-602
Opening the processor
Mounting of the cover (4 screws),
max. permissible tightening torque: 0.15 Nm
C6_2-019_641365_0506-e.p65
40
40
E
Connecting the
shield of the
PROFIBUS-DP cable
in the connectors
PG 11 on the
processor BIS C-602
BIS C-602
Mounting the PG connectors for PROFIBUS-DP
After connecting the (field) bus leads to the termional block, make sure that the shield has
proper connection to the PG housing.
Screw socket
Inside O-ring
Cable clamp
Screw the
swivel nut
with a torque
of 4.17 Nm
ca. 3 - 4 mm