Mooney 30, 30A, 30S Filter Instruction Manual  

|  1

© 2023 Baker Hughes Company. All rights reserved.

Product Description

The Type 30/30A/30S/ Mooney Filter is designed 

to remove dirt and other particulates in the pilot 

supply that could affect the resrictor or variable 

orifice in the pilot.

The Filter can be used in a variety of other gas and 

liquid applications.

Installation

The following instructions apply to mounting the Type 

30/30A/30S/ Mooney Filter on the Flowgrid regulator, 

FlowMax regulator and connecting to the pilot system. 

Refer to the Flowgrid regulator, FlowMax regulator, 

and Pilot IOM manuals for installation instructions and 

start-up procedures.

Figure 1 - The Type 30A Mooney Filter with Filter 

Housing removed allowing easy inspection of the 

element. Mounted on a 2” large single Port Flowgrid 

Regulator with Series 20 Pilot and Type 24 Restrictor.

1. Personnel:

 Installation of the Filter should be 

made by qualified personnel familiar with high 

pressure piping and pilot operated regulators.

2. Prior Inspection:

 Inspect the Filter for any damage 

that might have occurred in shipping. Make sure 

the body ports are clear of foreign material.

3. Orientation: 

The Type 30/30A/30S/ Mooney Filter 

should be installed with the Drain Plug down to 

allow drainage of liquids that may accumulate in 

the Filter Housing (Refer to Figure 2, page 2).

4. Filter Mounting:

 Apply pipe dope a 1/4 inch NPT 

schedule 80 seamless pipe nipple and mount filter 

by connecting the INLET connection on the filter to 

the body tap on the valve.

5. Filter Outlet:

 Run 3/8 inch tubing or 1/4 inch pipe 

from the filter OUTLET port to the INLET side of the 

restrictor in the pilot system of the regulator. The 

Type 30/30A/30S/ Mooney Filter has tow OUTLET 

ports for ease of tubing. Block the other port with 

the plug provided.

Note: To avoid galling when stainless steel 

to stainless steel connections are made, use 

a lubricant (such as NEVER SEEZ by Bostik). 

For best results, LIGHTLY lubricate the female 

threads. Mixing the lubricant with pipe dope is 

also acceptable. Do not exceed more than 1/4 turn 

past the point the threads start to bind.

Scope

This manual provides installation, operation and maintenance instructions for the Type 30/30A/30S/ 

Mooney

 

Filters. Instructions for the 

Flowgrid

 regulator, 

FlowMax

 regulator, and Pilot will be found in separate manuals.

Personal injury, equipment damage, or 

leakage due to explosion of accumulated 

gas or bursting of pressure containing parts, 

may result if this FILTER is overpressured, or 

is installed where service conditions could 

exceed the limits given in the specification of 

this manual, or on the nameplate, or where 

conditions exceed any ratings of the adjacent 

piping or piping connections. Verify the 

limitations of both valve and pilot to ensure 

neither device is overpressured. To avoid 

such injury or damage, provide pressure 

relieving or pressure limiting devices (as 

required by the Title 49, Part 192, of the U.S. 

code of Federal Regulations, by the National 

Fire Codes of the National Fire Protection 

Association, or by other applicable codes), 

to prevent service conditions from exceeding 

those limits. Additionally, physical damage 

to the valve/regulator, codes break the pilot 

or filter off the main valve, causing personal 

injury and/or property damage due to 

explosion of accumulated gas. To avoid injury 

and damage, install the filter in a safe location.