Mooney Flowgrid Slam Shut 1” valve Instruction Manual  |  5

Copyright 2021 Baker Hughes Company. All rights reserved.

Connection of any device such as a pilot to the 

inlet port on the valve body can result in the flow 

of gas downstream of the Slam Shut canceling the 

secondary downstream pressure protection of the 

slam shut. This may result in personal injury, death, 

equipment damage, and/or bursting of pressure 

containing parts and/or leakage of gas resulting in 

explosion of accumulated gas.

9.   

VENT VALVES AND GAUGE CONNECTIONS:

 Vent 

valves and gauge connections are recommended in the 

inlet and outlet piping to the Slam Shut and downstream 

regulator. These are a great convenience during start up, 

maintenance, and operation.

10.   

TOKEN RELIEF VALVES: 

Installation of a token relief valve 

in the line downstream of the Slam Shut is recommended. 

The relief valve should be set to open before the Slam Shut 

valve is set to close. Minor over pressure problems such as 

gas thermal expansion or seat leakage due to dirt moving 

through  the  system  will  be  handled  by  the  relief  valve, 

while maintaining a supply of gas to the customers. Major 

malfunctions of the regulator beyond the flow capacity of the 

token relief will activate the Slam Shut valve.

Set-up

Changing the Trip Set Point

1.  Remove the Adjusting Screw Cap
2.   Turn  the Adjusting  Screw  with  a  9/16”  wrench  to  change 

the set point. Turning clockwise will increase the setpoint 

pressure, turning counter-clockwise will decrease the 

setpoint pressure.

Resetting the Slam Shut (See Figure 4)

1.  Close the Upstream and Downstream Block Valves.
2.  Remove the bleed cap, reset cap, and clear bottom cap.
3.   Inside of the cavity labeled ‘bleed’, push and hold the pin 

with a screwdriver. This will cause the pressure upstream of 

the valve to bypass the shutoff device into the downstream 

piping, causing the pressure across the plug to equalize.

4.   If an Underpressure feature is being used, the line pressure 

must be 20% or more above the setpoint before resetting 

the valve. If an Overpressure feature is being used, the line 

pressure must be 20% or more below the setpoint before 

resetting the valve.

5.   Where the clear cap was previously located, find the shaft 

with a hole through it. Insert a screwdriver into the hole and, 

using the screwdriver as a handle, pull the shaft into the 

reset position.

6.   With the shaft held in the reset position, push the reset pin. 

The trip mechanism will then ‘snap’ into place.

7.   Replace  the  bleed  cap,  reset  cap,  and  clear  bottom  cap. 

(Make sure the reset pin remains in the ‘reset’ hole)

8.  Open the Upstream and Downstream block valves.

Testing Slam Shut Shutoff

During all Slam Shut shutoff tests, if a Flowgrid pressure regulator 

is  combined  with  the  Slam  Shut,  the  Flowgrid  must  be  in  the 

open position. There are two options to force the regulator open: 

(1) install a ball valve in the inlet tubing to the restrictor and close 

the valve to open the Flowgrid, or (2) disconnect and vent the 

inlet and outlet tubing.

Shutoff Test – Overpressure Protection Only (See Figure 5)

1.   Close upstream and downstream block valves and vent line 

pressure on inlet and outlet sides.

2.   Disconnect the Slam Shut sense line and plug the tubing 

connection in the piping.

3.   Connect a pressurized bottle into the Slam Shut sense line 

and introduce pressure above the Overpressure Set Point. 

The Slam Shut will trip closed.

4.  Disconnect the bottle and re-install the sense line tubing.
5.   Open the upstream block valve and monitor the downstream 

piping for any leakage.

6.   Go  through  the  ‘Resetting  the  Slam  Shut’  procedure  for 

Slam Shut reset.

Alternate Shutoff Test #1 – Overpressure Protection Only 

(See Figure 6)

1.   Must have a ball valve installed in the Slam Shut sense line 

& a tee between the ball valve and the Slam Shut.

2.   Close the Slam Shut sense line and vent the tubing.
3.   Connect  a  pressurized  bottle  into  the  tee,  and  introduce 

pressure above the Overpressure Set Point. The Slam Shut 

will trip closed.

4.  Disconnect the bottle and plug the tee.
5.  Open the Slam Shut sense line ball valve.
6.  Check the downstream piping for any leakage.
7.   Go  through  the  ‘Resetting  the  Slam  Shut’  procedure  for 

Slam Shut reset.

Alternate Shutoff Test #2 – Overpressure Protection Only

1.  Inlet and Outlet pipelines must have pressure.
2.   Remove the adjustment screw cap on the Overpressure 

Unit.3. Slightly loosen the nut on the adjusting screw. Do not 

change the location of the nut on the screw.

4.   Turn the adjustment screw counter-clockwise until the Slam 

Shut trips closed.

5.  Close the downstream block valve.
6.   Vent the downstream piping and monitor the downstream 

piping for any leakage.

7.   Turn the adjusting screw clockwise until the nut contacts the 

spring case. Tighten the nut.

8.   Go  through  the  ‘Resetting  the  Slam  Shut’  procedure  for 

Slam Shut reset.

Summary of Contents for Mooney Flowgrid Slam Shut

Page 1: ...Mooney Flowgrid Slam Shut 1 Valve Instruction Manual Rev D Baker Hughes Data Classification Public...

Page 2: ...ICULAR REQUIREMENTS FOR OPERATION OF OTHER EQUIPMENT AT THE SITE THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIBLE CONTINGENCY TO BE M...

Page 3: ...essure protection only 2 under pressure protection only and 3 over and under pressure protection Instructions for the Flowgrid regulator and Pilot are found in separate manuals Product Description The...

Page 4: ...ng Case Carbon Steel WCB Throttle Plate 17 4 PH or A515 Slam Shut Seat SST Slam Shut Seal Nitrile Flowgrid Diaphragm Nitrile or Viton Flowgrid Spring SST Slam Shut Housing Slam Shut Spring Cases Alumi...

Page 5: ...hut has all nitrile soft goods VITON The Slam Shut has nitrile static seals and viton dynamic seals and diaphragms MAX INLET Maximum inlet pressure PSIG BAR MIN DIFF Minimum difference in outlet and d...

Page 6: ...m Shut valve and or Flowgrid regulator should be made by qualified personnel familiar with high pressure piping and pilot operated regulators 2 Prior Inspection Inspect the Slam Shut valve regulator p...

Page 7: ...a handle pull the shaft into the reset position 6 With the shaft held in the reset position push the reset pin The trip mechanism will then snap into place 7 Replace the bleed cap reset cap and clear...

Page 8: ...bottle into the Slam Shut Sense Port and apply a constant pressure above the Underpressure set point and below the Overpressure set point if applicable See Figure 5 3 Follow the Resetting the Slam Sh...

Page 9: ...cy of the inspection and replacement of the parts depends on the severity of the service conditions and or the applicable government requirements Inspect all parts for wear and damage Replace all worn...

Page 10: ...dry Replacement of Seals in Underpressure Assembly 1 Turn adjusting screw 2 Use 1 2 wrench to remove four cap screws from spring case with Low Trip labeled on the actuator block 3 Use 9 16 wrench to...

Page 11: ...ccessories if applicable 2 Use 13 16 wrench to remove the four cap screws on the top plate 3 Remove the parts from the body 4 Inspect and or Replace the following seals Body Seals Qty 2 Re install dry...

Page 12: ...owgrid Sense Line Outlet Figure 9 Pressure reducing Flowgrid with Slam Shut downstream overpressure protection Figure 10 Pressure reducing Flowgrid with Slam Shut downstream underpressure protection S...

Page 13: ...over 60 psid 4 bar Inlet Flowgrid Sense Line Outlet Slam Shut Sense Line Outlet Outlet Inlet Flowgrid Sense Line Slam Shut Sense Line Inlet Outlet Outlet Slam Shut Sense Line Inlet Flowgrid Sense Lin...

Page 14: ...r Seal Plate O ring Damaged sealing surface Damaged Sense Port Adapter O ring Fails External Leakage Test out of Bleed Assembly Damaged Bleed Cap O ring Damaged Bleed Stem O ring Damaged Sealing Surfa...

Page 15: ...Mooney Flowgrid Slam Shut 1 valve Instruction Manual 13 Copyright 2021 Baker Hughes Company All rights reserved Notes...

Page 16: ...formation The Baker Hughes logo Flowgrid Slamshut and Mooney are trademarks of Baker Hughes Company Other company names and product names used in this document are the registered trademarks or tradema...

Reviews: