Consolidated 13900 Series POSRV Maintenance Manual
|
15
© 2018 Baker Hughes, a GE company. All rights reserved.
XI. Recommended Installation Practices (Contd.)
Table 2: Inlet Nut Torque Value
Flange Class
600 Class Flange
300 Class Flange
Area
in
2
cm
2
in
2
cm
2
200
1290
114, 143, 176
735, 923, 1136
Round
10% / -0%
ft-lb
N-m
ft-lb
N-m
1
25
33.9
25
33.9
2
75
101.7
75
101.7
3
150
203.4
150
203.4
4
300
406.7
300
406.7
5
500
677.9
500
677.9
6
800
1084.7
-
-
7
1100
1491.4
-
-
11
13
7
19
11
23
22
10
18
6
16
2
14
8
20
12
24
3
21
9
17
5
15
4
Figure 6: Inlet Nut Torquing Sequence
1. Refer to table for torque valve for applicable round.
2. Torque each nut in sequence shown.
3. Repeat for each round.
Table 3: Outlet Nut Torque
Bolts Diameter
1-1/8” (28.58 mm) Diameter Bolts
1-1/4” (31.75 mm) Diameter Bolts
Round
10% / -0%
ft-lb.
N-m
ft-lb.
N-m
1
25
33.9
25
33.9
2
75
101.7
100
135.6
3
150
203.4
300
406.7
4
355
481.3
500
677.9
1
16
6
10
4
14
8
12
2
15
5
9
3
3
7
11
1
16
6
18
10
4
14
8
20
12
2
15
5
17
9
3
13
7
19
11
Figure 7: Outlet Nut Torquing Sequence
Note: For 150 Class inlets, use bolting torques for 1-1/8” (28.58 mm) diameter bolts and Figure 7a
Figure 7a: 1-1/8” (28.58 mm) Diameter Bolts
Figure 7b: 1-1/4” (31.75 mm) Diameter Bolts