Electrical Control Function
60
Electrical Control System
Defrosting action
:
1.3.3.
4
Defrosting mode
:
AC will enter the defrosting mode according to the value of temp. of T3 and the value
range of temp. change of T3 and also the compressor running time.
Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will finish and the
machine will turn to normal heating mode.
----T3 rises to be higher than TCDE1
℃
.
----T3 keeps to be higher than TCDE2
℃
for 80 seconds.
----The machine has run for 15 minutes(18~24K) or 10 minutes (36~60k) in defrosting
mode.
no longer than 10min
60s
on
10s
F8
30s
Compressor
F2
off
4-way valve on
off
Outdoor fan on
Off
Indoor fan on
off
breeze 10s