Electrical Control Function
56
Electrical Control System
Outdoor fan in low temperature cooling mode acts as follow:
T3
38
Off
Low
30
27
23
Exit low temperature
cooling mode
,
High
fan running for 1
minute
1.3.2.3 Indoor fan running rules
In cooling mode, indoor fan runs all the time and the speed can be selected as high, (medium), low and auto.
The auto fan:
4
T1-Ts
3
High
Low
1
Medium
1.5
Setting fan
speed
Actual fan speed
H+(H+=H+G)
A
H(=H)
B
C
M+(M+=M+Z)
D
M(M=M)
E
F
L+(L+=L+D)
G
L(L=L)
H
I
T1-Td
℃
(°F)
L
L-(L-=L-D)
H
H-(H-=H-G)
M
M-(M-=M-Z)
The auto fan acts as below rules:
T1-Ts
High
Low
Medium