INTRODUCTION
I-E96-508C
D - 1
APPENDIX D - MODULAR POWER SYSTEM SIZING TABLES
INTRODUCTION
The tables in this appendix enable you to size the modular
power system and bypass the calculations required by the siz-
ing procedure in
. Use Table
to size power sys-
tems that have only IEPDS01 and IEPDS02 modules. To use
the tables, first determine the current requirements for the
cabinet (refer to
). Shown in the table are values for
A (5 VDC current requirement for the cabinet) and B (24 VDC
current requirement for the cabinet). The box intersected by
the requirements of A and B shows the number of PDS mod-
ules needed.
Table D-1. Q1 for Systems Using IEPDS01/02 Modules Only
A
B
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
5
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
10
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
15
2
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
20
2
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
25
3
3
3
3
4
4
5
5
6
6
7
7
8
8
9
9
30
3
3
3
3
4
4
5
5
6
6
7
7
8
8
9
9
35
4
4
4
4
4
5
5
6
6
7
7
8
8
9
9
10
40
4
4
4
4
4
5
5
6
6
7
7
8
8
9
9
10
45
5
5
5
5
5
5
6
6
7
7
8
8
9
9
10
10
50
5
5
5
5
5
5
6
6
7
7
8
8
9
9
10
10
55
6
6
6
6
6
6
6
7
7
8
8
9
9
10
10
11
60
6
6
6
6
6
6
6
7
7
8
8
9
9
10
10
11
65
7
7
7
7
7
7
7
7
8
8
9
9
10
10
11
11
70
7
7
7
7
7
7
7
7
8
8
9
9
10
10
11
11
75
8
8
8
8
8
8
8
8
8
9
9
10
10
11
11
12
80
8
8
8
8
8
8
8
8
8
9
9
10
10
11
11
12
85
9
9
9
9
9
9
9
9
9
9
10
10
11
11
12
12
90
9
9
9
9
9
9
9
9
9
9
10
10
11
11
12
12
95
10
10
10
10
10
10
10
10
10
10
10
11
11
12
12
13
100
10
10
10
10
10
10
10
10
10
10
10
11
11
12
12
13