MODULE POWER REQUIREMENTS
CALCULATING CURRENT REQUIREMENTS
B - 2
I-E96-508C
4. Calculate the -15 VDC current requirement for each cabi-
net.
a. Refer to Table
for the -15 VDC current requirement
of each module.
b. Total the -15 VDC current requirement per cabinet.
5. Calculate the 24 VDC current requirement.
a. Refer to Table
for the 24 VDC current requirement
for each module.
b. Table
lists 24 VDC current requirements of termi-
nation units and termination modules.
c.
Total the 24 VDC current requirement per cabinet.
6. Add the current requirement of any system powered I/O
using 24 VDC to the total from Step 5c. The procedure under
CALCULATING I/O CURRENT REQUIREMENTS
gives an over-
view of how to calculate the system powered I/O current
requirement.
Table B-1. DC Current Consumption for INFI 90 Modules
INFI 90
Modules
No. of
Modules/
Cabinet
Current Consumption per Module (mA)
5 V
Total
5 V
+15 V
Total
+15 V
-15 V
Total
-15 V
24 V
Total
24 V
IISAC01
0
0
0
530
IMAMM03
725
125
30
0
IMAOM01
1045
0
0
0
IMASI02
95
30
25
0
IMASI03
330
140
40
0
IMASM01
120
85
45
0
IMASM02
IMASM03
400
80
40
6
IMASM04
550
45
30
0
IMASO01
530
220
225
50
IMCIS02
300
30
25
7
IMCOM03
IMCOM04
660
55
50
7
IMCPM01
0
0
0
0
IMCPM02
825
0
0
0
IMDSI02
60
0
0
0
IMDSM04
1500
0
0
65
IMDSM05
600
0
0
0
Page total