(continued)
Line regulation
0.5%
Hold up time
≥
6 msecs (output fully loaded)
Heat dissipation
120 BTU per hr
IEPEP04 Power Entry Panel Characteristics
Input voltage
21 VDC (min.) to 30 VDC (max.) for 24 VDC input
42 VDC (min.) to 60 VDC (max.) for 48 VDC input
Ripple voltage
The input voltage range includes RMS ripple voltage.
Maximum input current
60 A for 24 VDC input
30 A for 48 VDC input
Maximum input interruption
6 msecs
Maximum input line surge
36 V for 24 VDC input (not to exceed 5 msecs)
65 V for 48 VDC input (not to exceed 5 msecs)
Redundant DC transfer time
7 msecs typical
Voltage monitor inputs
Power system alarm output
Open to alarm, 24 VDC maximum, 120 mA
(inductive loads require diode suppression)
Bus voltage alarm output
Open to alarm, 24 VDC maximum, 120 mA
(inductive loads require diode suppression)
Status signal inputs
Normally open (NO) or normally closed (NC) jumper selectable on BMM
module, low
≤
0.8 VDC, high
≥
3.1 VDC
General
Electromagnetic/radio
frequency interference
Values not available at this time. Keep cabinet doors closed. Do not use
communication equipment any closer than 2 m from the cabinet.
Mounting
Power supply modules occupy one slot in the INFI 90 module mounting unit
(MMU) or power mounting unit (PMU). Fastens to MMU or PMU with two
half-turn latches on the faceplate.
Physical dimensions
Table 1-4. Specifications
(continued)
Property
Characteristic/Value
Bus
Valtage
(VDC)
Trip Point,
Typical (VDC)
DC MPS bus
5
4.76
15
14.3
-15
-14.3
24
24.5
Auxiliary bus
24
21.8
48
43.7
125
114
Device
Dimensions
Height
Width
Depth
mm
in.
mm
in.
mm
in.
IEFAN03/05
44.4
1.75
482.6
19
330.2
13
IEMMU01/02
177.8
7
482.6
19
317.5
12.5
IEPEP04
175.2
6.9
482.6
19
685.8
27
IEPMU01/02
177.8
7
482.6
19
317.5
12.5