INSTALLATION
IEPEP04 POWER ENTRY PANEL WIRING
I-E96-508C
3 - 5
2. Connect 24 VDC or 48 VDC primary (L1) input power to
TB3 (+), TB4 (-) and TB5 (GND) (Figure
3. Connect the secondary (L2) DC power input (if used) to
TB5 (GND), TB6 (-) and TB7 (+). Both inputs must be the same
nominal voltage level. If only 1 DC power input is being used,
proceed with Step 4. If not, skip to Step 5.
4. Connect TB3 to TB7 and TB4 to TB6. Use 6 AWG wire.
Note that this step avoids false status information because it
connects line 1 and line 2 inputs together.
5. Connect cable 6637813_1 from J2 on the power entry
panel to the system power bus bar. This provides connections
to sample the DC output bus voltages, monitor the power mod-
ule status signal and to output a power fail interrupt signal.
See the wiring diagrams at the end of this manual (Figure
for correct system power bus bar connections.
6. Connect cable 6639443_1 from TB8, TB9, TB10, TB11 and
TB12 on the panel to the input power bus bar for distribution
of DC power to the module mounting unit (Figure
).
7. Connect cable 6637818_2 from the input power bus bar to
each module mounting unit backplane (Figure
).
8. Connect the fan assembly power cable to connector J1
labeled FAN OUT on the panel (Figure
9. Connect a wire equivalent to power wiring but not less
than 6 AWG from the TB10 (GND) stud of the panel to the cab-
inet frame for DC input safety grounding (Figure
10. There are 2 extra voltage monitor inputs available to moni-
tor customer external power supply voltages (see Figure
Use terminal block TB2 labeled AUX BUS MONITOR for this
purpose. Attach one input to terminals 1(+) and 2(-) labeled
CH1. Connect the other input to terminals 3(+) and 4(-) labeled
CH2. Inputs can be 24 VDC, 48 VDC or 125 VDC. Set jumpers
J1 and J2 for the desired voltage. Refer to Table
11. Wire the status inputs to terminal block TB1, terminals 1
(STATUS IN 1), 2 (COM) and 3 (STATUS IN 2). Insure that the
inputs are open collector or contact type referenced to DC
common (terminal COM). The alarm inputs must have the cur-
rent carrying capability to sink at least 1 mA. If the system
uses Plant Loop, do Step 12. If not, go to Step 13.
12. Connect cable 6634205_1 from TB1 terminal 4 STATUS
OUT to the P3 card edge connector of the bus interface module
(BIM). Doing so enables the BIM to send the status message to