INSTALLATION
I-E96-416B
2 - 5
Make connections to the termination unit after it is mounted in
the field termination panel. To install the cable follow these
steps.
1. Verify slave module (IMASM01, IMASI02 or IMFBS01) is
unplugged from the MMU backplane.
2. Insert the hooded end of an NKTU01 or NKTU11 cable into
the MMU backplane slot assigned to the slave module. The
cable should latch securely in place. Card edge connector P3 of
the slave module connects to this end of the cable.
3. Insert the male 36 pin connector end of the NKTU01 or
NKTU11 cable from the slave module into the P1 connector of
the termination unit. The cable should latch securely in place.
4. Slide the slave module into the module mounting unit until
the module is fully seated and the faceplate is flush with the
front of the rack.
Terminal Block Wiring
Connect the wiring to the termination unit terminals from the
input devices sensing the process. Input devices may be: BC/
BCN series Bailey Controls Pressure Transmitters, EQ/EQN
series Bailey Controls Temperature Transmitters, pH series
Bailey Controls pH/TBN Transmitters or any conventional
transmitter. See Figure
for an example of an NTAI05 input
circuit.
Field wiring should be 12 to 22 AWG wire. Refer to the
Site
Planning and Preparation
manual for information on field
wiring such as noise immunity and spacing requirements.
CAUTION
Remove modules from their module mounting unit slots before
installing or removing a cable assigned to that slot. Failure to
do so could result in damage to the module.
ATTENTION
Retirer le module de son emplacement dans le chassis de
montage des modules avant d'installer ou de retirer un câble
assigne a cet emplacement. Un manquement à cette procédure
pourrait endommager le module.