INSTALLATION
SETUP/INSTALLATION
2 - 6
I-E96-405A
®
Power Wiring
There are five terminals that provide power and ground con-
nections. See Figure
for terminal locations. Terminal E4 is
the +24 VDC power connection. Terminal E2 is the I/O com-
mon. Terminal E1, E3 and E5 are shield connections.
Make power connections to the TU after it is mounted in the
NFTP01. Make sure cabinet and I/O power are turned off
before connecting ground and power wiring. Refer to the follow-
ing steps when installing the TU into a cabinet that uses the
modular power supply system.
1. Attach a 14 AWG wire from the +24 VDC power source
within the cabinet or an ex24 VDC source to the E4 ter-
minal on the TU.
2. Attach one 14 AWG wire from the DC bus bar at the bottom
of the cabinet to the E2 terminal (I/O common) of the TU.
Figure 2-3. Terminal Assignments and Input Example for NTAI04
JUMPERS TO
SELECT
RESISTANCE
(CALIBRATION),
ZERO AND SPAN
FIELD I/O TERMINATION
BLOCKS (TB1-TB4)
A
B
C
A
B
C
A
B
C
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
5
6
7
8
5
6
7
8
1
2
3
4
1
2
3
CH
P3
P1
P2
NTAI04
CH
4
TYPICAL
CONNECTION
FOR AN RTD TO
AN NTAI04 INPUT
JUMPERS TO
SELECT
CHANNEL TO BE
CALIBRATED
P2 SOCKET FOR
NKTU01 CABLE
TO ASM
P3 SOCKET FOR
CALIBRATION
P1 SOCKET FOR
NKTU01 CABLE
TO ASM
E2 COMMON
F1 0.25-A
FUSE
E4
+24 VDC
E5 SHIELD
FOR P2
SOCKET
E1 SHIELD
FOR P1
SOCKET
T00469A
E3 SHIELD
FOR P3
SOCKET
TB4
TB3
TB2
TB1