INSTALLATION
SETUP/INSTALLATION
I-E96-405A
2 - 3
2. Insert the termination unit tabs into the slots in the outside
edge of the termination panel.
3. Mount the TU to the field termination panel with 2, number
10,¾ inch screws. Do not over-tighten the screws. See Figure
2-1.
Cable Connections
The NTAI04 has three cable connectors, P1, P2 and P3. Con-
nector P1 and P2 connect through separate communication
TU cables to two slave modules. Connector P3 connects
either TU cable to calibrate the slave inputs. Install the
NKTU01 and NKTU11 cable into P1 and P2 connectors on the
TU. The NKTU01 and NKTU11 is a round, shielded cable that
connects the TU to the IMASM03and IMASM04 slave module.
The NKAS01 cable has a PVC jacket and is rated for 80
degrees Celsius at 300 volts (UL rated type CL2). The
NKAS11 cable has a non-PVC jacket and is rated for 90
degrees celsius at 300 volts (UL rated type PLTC). See
Figure 2-1. Installation for NTAI04
TB1
TB2
TB3
TB4
TB4
TB3
TB2
TB1
FIELD TERMINATION PANEL
MOUNTING SCREWS
T00464A
TABS
STANDOFF