Power Supply
Voltages:
± 5 VDC Logic Supply ± 5%
± 24 VDC I/O 12%, -10%
Current Consumption:
5 VDC
1.4 Amps typical, 1.5 Amps maximum
24 VDC
62 mA typical, 70 mA maximum
Inputs
Input Voltages:
Range 1, 5 VDC Supply: 4.0 VDC to 6.0 VDC
Range 2, 24 VDC Supply: 21.6 VDC to 27.0 VDC
Range 3, Preamplifiers:
50 mV (peak to peak)
to 10 V (peak to peak)
Max. Input Signal Current
at Max. Input Voltage:
Range 1:
14.8 mA at 6 VDC
Range 2:
8.4 mA at 24 VDC
Range 3:
0.4 mA at 10 V (peak to peak)
Logic 1 Input Voltages:
Range 1:
4 VDC minimum, 6 VDC maximum
Range 2:
21.6 VDC minimum, 27 VDC maximum
Range 3:
25.0 mV peak minimum, 5 V peak maximum
Logic 0 Input Voltages:
Range 1:
0 V minimum, 1.0 V maximum
Range 2:
0 V minimum, 2.0 V maximum
Range 3:
-5 V peak in., -25.0 mV peak maximum
Debounce Times
ON time 8.5 milliseconds (typical)
OFF time 8.5 milliseconds (typical)
Input Signal Frequency Limit Upper frequency limit for using debounce: 40Hz
Mode Accuracy
Totalize: ± 0 Counts
Frequency Count: ± 1 Count
Period Determination: ± 1 Count
Maximum Input Frequency
50 kHz (at 50% duty cycle)
Timebase Accuracy
±
0.033%
Isolation Voltage
150 V RMS channel to channel
350 V RMS inputs to logic
Surge Withstand
Meets requirements of IEEE Surge Capability Standard 472-1974,
on all debounced inputs
NOTE: If you select a preamplifier for a channel, the counter associated
with that channel may increment during surge pulsing.
Mounting
Uses 1 slot in Infi 90 Module Mounting Unit.
Environmental
Electromagnetic/
Radio Frequency
Interference
No values available at this time.
Keep cabinet doors closed. Do not use communication equipment closer
than 2 meters from the cabinet.
Ambient Temperature
0
o
to 70
o
C (32
o
to 158
o
F)
Relative Humidity
5% to 95% up to 55
o
C (131
o
F) (non-condensing)
5% to 45% at 70
o
C (158
o
F) (non-condensing)
Atmospheric Pressure
Sea level to 3 km (1.86 miles)
Air Quality
Noncorrosive
Certification
CSA certified for use as process control equipment in an ordinary
(nonhazardous) location.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE