NIDI01 TERMINATION MODULE CONFIGURATION
CONFIGURING INPUTS FOR NIDI01
B - 2
I-E96-308A
®
CONFIGURING INPUTS FOR NIDI01
Installing the NIDI01 includes these steps: setting up the com-
patibility jumpers (J1 through J10), connecting the termina-
tion unit cable, connecting the power supply and connecting
the input circuits. Jumpers J1 through J10 must be config-
ured to make the NIDI01 compatible with the DSM. For this
application, jumpers J1 through J9 should be broken. If the
preamplifiers on the DSM input channels 1 and 2 are not
going to be used, break jumper J10. Figure
shows the ter-
mination assignments for the termination unit. Figure
shows the jumper configuration For NIDI01.
CONNECTING THE POWER SUPPLY FOR NIDI01
The power supply connection to the NIDI01 only needs to be
made if you use the preamplifiers on the DSM input channels
1 and 2. Input circuits cannot be powered through the termi-
nation unit. They must be externally powered. If you use the
preamplifiers, connect the 24 VDC I/O power supply positive
terminal to terminal 2 of the NIDI01. Then connect the com-
mon power supply lead to terminal 1 of the NIDI01. Use num-
ber 14 AWG multi-stranded wire. Figure
shows the
connections for the power supply. Figure
shows the cable
connections for the NIDI01.
Figure B-2. Termination Assignments for NIDI01
1
2
3
5
6
7
8
9
10 11 12 13 14 15 16 17 18
4
19 20 21 22 23 24 25 26 27 28 29 30 31 32
TERMINAL NUMBER
MODULES USING NIDI01
IMDSM04
–
–
–
–
–
+
+
+
+
8
4
7
NOT USED
NOT USED
3
6
2
5
1
+
+
+
+
–
–
–
C
O
MMO
N
+2
4
V
D
C
TP35723A
Application
Signal Type
Number of
I/O
Jumper Configuration
J1 - J10
Connecting
Cable
0 to 6 VDC
0 to 27 VDC
-5 to +5 VDC
8/0
NKTM01
or
NKTU02
Figure B-3. Configuration Summary for NIDI01
TP21513A
1
2
3
4
5
6
8
7
9 10