INTRODUCTION
WBPEEUI240755B0
5 - 1
SECTION 5 - TROUBLESHOOTING
INTRODUCTION
This section explains the error indications and corrective
actions for the IMCIS12 and IMQRS12 modules.
ERROR INDICATIONS AND CORRECTIVE ACTION
Status of the CIS and QRS modules can be obtained through
an INFI 90 OPEN operator interface (e.g., Operator Interface
Station, Engineering Work Station, Configuration and Tuning
Terminal) or the front panel module status LED indicators.
When using an operator interface, check the control module
for good quality on output N+9 of function code (FC) 79; 0 =
good status, 1 = bad reference status, I/O failed to respond.
Status LED
The front panel status LED has three states to indicate normal
operation and error conditions. Table
lists status LED
states, error indications, probable causes and corrective
actions.
NOTE:
If the corrective actions in Table
do not correct a problem
with the CIS or QRS module, replace the module.
Table 5-1. Status LED Indications and Correction Actions
LED State
Indication
Probable Cause
Corrective Action
Solid Green
(POWER)
I/O module operating
normally and communi-
cating with MFP
Normal operation
No action required
Off
I/O module not enabled Address set on address
switch S1 not the same
as address in MFP con-
figuration FC 79, spec
S1
Change address on address switch S1 to
correspond with FC 79, spec S1
- or -
Change address in FC 79, spec S1 to
correspond with address switch S1
Dipshunt not properly
installed between MFP
and I/O module
Verify dipshunt is installed properly (no
bent pins) in I/O expander bus socket on
MMU backplane between MFP and I/O
module
MFP configuration is
not correct
Verify FC 79 is in MFP configuration
No power to I/O module Module not completely
inserted in MMU
Verify module is completely inserted in
MMU: faceplate flush with MMU and cap-
tive retaining screws latched
Red
(FAIL)
Bus fault timer error
(time-out)
I/O expander bus clock
failure
Check MFP for proper operation