TROUBLESHOOTING
MODULE PIN CONNECTIONS
WBPEEUI240757A0
5 - 3
The MFP generates a
MISSING SLAVE MODULE
error if the I/O
expander bus is not connected between it and the ASO module.
Verify the bus connection on the MMU backplane.
If you determine the I/O module is faulty, replace it with a new
one. Refer to
for procedures to replace an ASO module.
MODULE PIN CONNECTIONS
The ASO module has three connection points for external sig-
nals and power (P1, P2 and P3). Tables
,
and
show
the pin connections.
WARNING
Disconnect power before installing dipshunts on the MMU
backplane. Failure to do so will result in contact with cabinet
areas that could cause severe or fatal shock.
Table 5-2. P1 Power Pin Connections
Pin (P1)
Connection
Pin (P1)
Connection
1
2
3
4
5
6
+5 VDC
+5 VDC
NC
NC
Common
Common
7
8
9
10
11
12
+15 VDC
-15 VDC
PFI
PFI
NC
NC
PFI=Power Fail Interrupt
NC=Not Connected
Table 5-3. P2 Expander Bus Connections
Pin (P2)
Signal
Pin (P2)
Signal
1
2
3
4
5
6
Data 1
Data 0
Data 3
Data 2
Data 5
Data 4
7
8
9
10
11
12
Data 7
Data 6
Clock
Sync
NC
NC
NC=Not Connected
Table 5-4. P3 Output Pin Connections
Signal
Pin(+)
Pin(-)
Signal
Pin(+)
Pin(-)
AO1
AO2
AO3
AO4
AO5
AO6
AO7
NC
A
B
C
D
E
F
H
—
1
2
3
4
5
6
7
8
AO8
AO9
AO10
AO11
AO12
AO13
AO14
+24 VDC
K
L
M
N
P
R
S
J
9
10
11
12
13
14
15
—
AO=Analog Output