Initial operation
6.1
Configuration
The configuration of the motor control box is set via the potentiometers P1 and P2,
the configuration switch and the reset key.
N O T I C E
Overtightened potentiometer
Damage of control device may result in malfunction.
Potentiometers have a right and a left stop, which must not
be overtightened.
Adjust potentiometer only with low force and with an
appropriate screw driver.
Hint
When the motor control box is used without encoder, a change in
configuration requires a new initial operation.
Set up desired configuration, according to chapter 6.1.3
Do initial operation.
Refer to chapter 6.2
Configuration is set during initial operation.
Hint
Changes of the automatic close delay or the tolerance of the power
operated shutdown are applied instantly.
6.1.1
Automatic closing delay time
The automatic closing delay time determines the time the door stays open in
automatic operation mode. After the delay time, the door closes automatically. The
delay time is set via the potentiometer P1 in a range of 5 to 60 seconds.
Turn potentiometer 1 (P1) clockwise
Door stays open for a longer time.
Turn potentiometer 1 (P1) counterclockwise
Door stays open for a shorter time.
Changing the
configuration
Prolongen automatic
closing delay time
Reduce automatic
closing delay time