HOW TO ASSEMBLE AND
INSTALL THE  PC100XP

This section deals with the procedures and recommen-

dations on how to install Badger’s PC100XP electronic
batch controller in hazardous locations.

Except for the assembly and installation procedures, all

other instructions are identical to the standard PC100 and
should be referred to in this manual.

DESCRIPTION

The PC100XP is a standard batch controller mounted in

an explosion proof enclosure. The enclosure is FM ap-
proved for CLASS 1, DIVISION 1, GROUPS C & D and CLASS
II, GROUPS E, F & G environments. The enclosure complys
with CSA and UL standards. It is also rated for NEMA 3, 4,
7 & 9 service (watertight).

OPERATION

The operation of the PC100XP is identical to that of the

PC100 controller. On the PC100XP model, programming of
functions and control commands is done mechanically
through explosion proof push buttons.

Note:  To prevent accidental or unauthorized tampering,

deactivate all programming or command functions (except
for those required during production operation) using func-
tion #41.

UNPACKING

The PC100XP is shipped from the factory disassembled.

The standard PC100 and the XP enclosure are shipped
separately to facilitate installation and wiring.

ASSEMBLY

ALWAYS FOLLOW LOCAL CODES AND MANUFAC-

TURER’S INSTRUCTIONS WHEN INSTALLING THIS AND
OTHER TYPES OF EQUIPMENT IN HAZARDOUS ENVI-
RONMENTS.

Note:  Operating temperature is 32° F to 130° F with a

maximum humidity of 85% non-condensing. Select a mount-
ing location with proper ventilation.

Warning:  To prevent the danger of electrical shock or

explosion, turn off the power in any circuits that may
introduce power to the wiring during the installation of this
controller.

STEP-BY-STEP INSTALLATION

The following step-by-step installation instructions

should be regarded only as a guideline for proper instal-
lation. Local codes or practices may require additional
functions to be performed in order to assure safety of
installation and operation.

1. Using a 1/4" allen wrench, remove the cover bolts from

the front cover. Carefully place the cover over a level
surface.

2. Unscrew the mounting plate screws and remove the

Mounting plate.

5

3. Open the PC100 carton and remove the unit. Use the

enclosed mounting clips to mount the PC100 to the
mounting plate.

4. Using the bottom and/or side tapped holes, mount the

XP housing onto a firm platform, cabinet or the wall.

Upon completion of all wiring, tightly close all enclo-

sures within the system.

Before applying power to the system:

• All electrical connections must be secure.
• All seals must be properly poured and completely

cured and their seal fittings tightly closed.

• All joints in the conduit run must be tight.
• All enclosures in the system must be tightly closed.

Apply power to the controller and test operation in a

manner that is suitable for the particular application. Ex-
ercise extreme caution!

For technical assistance during or after installation,

please call our sales department or contact the Badger
Meter representative in your area.

Summary of Contents for PC100

Page 1: ...n Manual BadgerMeter Inc Model PC100 SERVICE INFORMATION FILE MANUAL FOR FUTURE REFERENCE AND SERVICE Serial Number Date Installed Service Line Operator IMPORTANT Read this manual before attempting an...

Page 2: ...2...

Page 3: ...OPTIONAL PROGRAMMING Display FLOW RATE instead of BATCH COUNT 13 LIMIT the batch size that can be programmed 15 AUTORECYCLE to repeat batches automatically 15 AUTOADJUST to compensate for valve overr...

Page 4: ...put 17 Start Command 35 Serial Data Output 18 Pulse Input Doubler 36 Serial Data Output CAUTION Topreventaccidents powerconnectionshould HOW TO UNPACK ASSEMBLE AND INSTALL THE PC100 4 Note K1 relay co...

Page 5: ...a maximum humidity of 85 non condensing Select a mount ing location with proper ventilation Warning To prevent the danger of electrical shock or explosion turn off the power in any circuits that may i...

Page 6: ...ng transmitter input 2 on terminal 10 EPT1XP PEPT1 TYPE B These models require that a special current regulator supplied with the transmitter be installed exactly as shown Reversing the polarity will...

Page 7: ...stage for final valve shutdown OPTIONAL APPLICATIONS FEED PUMP CONNECTION Relay K1 can be connected to a feed pump to inject or add fluidstothemainbatchonapresettimebasis RefertoF32 HI AND OR LOW FLOW...

Page 8: ...Batch Signal Can be used to totalize batches or cycle runs during a period of time or to cascade several PC100s so that one PC100 can start when the other finishes This signal duration is adjustable F...

Page 9: ...input of the next unit Serial connection will be interrupted to all units if the power supply fails on any one of the PC100s To prevent this from happening you may want to connect a communications rel...

Page 10: ...eturn the display to batch count The 5 key is used to display the instanta neous flow rate in GPM LPM etc The 0 key is used to RESUME operation from the point where a STOP command was received To View...

Page 11: ...ode Enable 13 35 Serial Output Select Pulse or Information 17 36 Pulse Output Width 1 to 99 ms 13 37 Rate Output Latch 16 lower digits ProgramingthePC100isverysimple Exceptforprogram ming batch preset...

Page 12: ...talize the number of batches run for a period of time day week year or shift If connected to terminal 17 a second PC100 it can be used to start The display will show Once all wiring has been completed...

Page 13: ...ction is activated code 1 the PC100 can only be used as a rate indicator and totalizer All batch functions will be inactive The display will default to rate of flow FUNCTION 18 SCALE FACTOR CALCULATIO...

Page 14: ...nctions by scrolling up or down but you will not be able to enable or disable them To operate this function press FUNCTION 41 ENTER At this point you will see the three digits to the right The two dig...

Page 15: ...prewarn signal is used to control an alarm or a feed pump the signal duration can be programmed from 1 to 99 seconds Never use the time out if K1 is connected to the first stage of a valve FUNCTION 1...

Page 16: ...etpoint is lower than the Hi setpoint If not the display will flash zeros and if con nected to a printer or computer an ERROR message will be transmitted FUNCTION 37 RATE OUTPUT LATCH The choices are...

Page 17: ...1 second and 1 for 1 second FUNCTION 63 PRINT ON START AND OR STOP Program 1 to print on START Program 2 to print on STOP Program 3 to print both on START and on STOP FUNCTION 64 PRINT COMMAND Progra...

Page 18: ...visible count on the display when scale factor 1 5 Wrong scale factor 5 Check scale factor calculation i e if programmed 0001 instead of 1 0000 unit will wait for 1000 pulses before decrementing count...

Page 19: ...the unit is still not functioning appropriately There is the possibility that some internal component has been damaged and it is preventing normal operation At this point it is recommended that you ru...

Page 20: ...ithout notice except to the extent an outstanding bid obligation exists BadgerMeter Inc P O Box 245036 Milwaukee WI 53224 9536 Telephone 414 355 0400 877 243 1010 Fax 414 355 7499 866 613 9305 www bad...

Reviews: