background image

Page 12

 

      

 6-11

Series 3050 Btu Monitor

Solid State Switch and Form “C” Output Wiring 

The Series 3050 Btu Monitor has one Normally Open (N.O.) solid state switch, and one solid state form “C” relay.

Check the Specifications on page 29 for maximum voltage and current ratings for each type output. These outputs are 

completely independent, electrically isolated, and can be programmed as either Pulse or Set Point outputs.

When the “Totalizer” function is selected, the unit of measure and resolution are independent from the displayed units and 

can be programmed where one pulse occurs once every 0000000.1 to 999999999. of units selected, with any pulse width 

from 0001 to 9999mS.

When the “Alarm” is selected as the unit of measure and the resolution is independent from the displayed units, it allows the 

unit to be programmed as either a high or low rate Set Point. Since the Set Point, Release Point and their associated time 

delays are fully independent, this output can be either a classical high rate or low rate alarm, depending on the settings 

selected. When design planning, keep in mind that although both of these outputs can be programmed as alarm points only, 

the relay provides both N.O. and N.C. contacts. The switch is a simple N.O. contact.

Examples:

High Flow Set Point Control

The Set Point must be a value greater than the Release Point. 

The relay output will have continuity between its N.C. terminal and “COM” until the flow has exceeded the Set Point (“SETPT”)  

for a continuous period of time exceeding the Set Point Delay (“SDLY”), at which time the N.C. connection will open and the 

N.O. contact will have continuity to the “COM” terminal. When the flow has dropped below the Release Point (“RELP") for a 

continuous period of time exceeding the Release Point Delay (“RDLY”), the relay states will return to their original states. If the 

latch has been set to “ON”, the relay will not release until manually reset once the Set Point and Set Delay have been satisfied. 

Sources for the Set Point control can be Flow Rate, Energy Rate, T1, T2 or Delta T.

Low Flow Set Point Control

The Set Point must be a value less than the Release Point. 

The relay output will have continuity between its N.C. terminal and “COM” until the flow drops below the Set Point (“SETPT”) 

for a continuous period of time exceeding the Set Point Delay(“SDLY”), at which time the N.C. connection will open and the 

N.O. contact will have continuity to the “COM” terminal. When the flow has again risen above the Release Point (“RELP”) for a 

continuous period of time exceeding the Release Point Delay (“RDLY”), the relay states will return to their original states. If the 

latch has been set to “ON”, the relay will not release until manually reset once the Set Point and Set Delay have been satisfied. 

Sources for the Set Point control can be Flow Rate, Energy Rate, T1, T2 or Delta T.

 

1  RELAY 1 NO

2  RELAY 1 NC

3  RELAY 1 COM 

4  PULSE 1 OUT

5  PULSE 2 OUT

Figure 9: Relay and Switch Wiring Examples

Summary of Contents for Impeller Data Industrial 3050 Series

Page 1: ...Series 3050 Data Industrial Series 3050 Btu Monitor Installation Operation Manual 941700 0030 6 11 IMPORTANT This manual contains important information READ AND KEEP FOR REFERENCE...

Page 2: ...Series 3050 Btu Monitor Page ii 6 11...

Page 3: ...N 7 Mechanical Installation 7 Location 7 Electrical Installation 8 OUTPUT OPTION CARD 14 DISPLAY AND KEY PAD 16 PROGRAMMING 17 Selection Screens 17 Option List Screens 17 Data Screens 17 USB Communica...

Page 4: ...Series 3050 Btu Monitor Page iv 6 11...

Page 5: ...ithin 48 hours of delivery and file a claim with the carrier A claim for equipment damage in transit is the sole responsibility of the purchaser Product Description The Badger Meter Data Industrial Se...

Page 6: ...e fully programmable as either Pulse Volume or Set Point control based Flow Rate Flow Total Energy Rate Energy Total Temperature 1 Temperature 2 or Delta T For pulse output the installer can program b...

Page 7: ...ven to cooling or ventilation However prolonged direct sunlight can damage the front panel so some level of shading is recommended especially if installed in a tropical climate Panel Mount Installatio...

Page 8: ...olt Amp requirements A fused circuit is always recommended Connect the positive of the power supply to the Series 3050 terminal marked ACL DC and connect the negative of the power supply to the Series...

Page 9: ...DI Used for all Badger Meter Data Industrial Flow Sensors Provides an internal pull up resistor and uses K and Offset values for calibration Pulse K Factor Accepts non zero crossing inputs but provid...

Page 10: ...ut for current inputs optimizes performance and flexibility or loop power supplies Both the low and high end scaling are independent and field configured by the installer NOTE See the Programming Flow...

Page 11: ...e Thermistors and RTD s Wiring Three Wire RTD s 1 TEMP 1 IN 2 TEMP 1 IN 3 TEMP 1 GND 4 SHIELD 5 TEMP 2 GND 6 TEMP 2 IN 7 TEMP 2 IN Jumpers 2 Wire Thermistor Located in same Supply or Return line Flow...

Page 12: ...have continuity between its N C terminal and COM until the flow has exceeded the Set Point SETPT for a continuous period of time exceeding the Set Point Delay SDLY at which time the N C connection wi...

Page 13: ...2 OUT Figure 10 Relay and Switch Wiring Examples continued Chiller Control Based on High Energy Usage with Indication Figure 8 Relay and Switch Wiring Examples continued Chiller Control based on High...

Page 14: ...Series 3050 has special software that permits the Analog output 2 USB for direct access to a computer using a standard mini USB cable 3 RS 485 for fully addressable Modbus or BACnet communication 1 R...

Page 15: ...e Standard Cable USB Type A Male To Type Mini B 5 Pin Male Connect to Computer USB Com Port Model 3700 Model 345WT or other MODBUS Master Device Shield RS485 RS485 1 RS485 B 2 RS485 A 3 RS485 GND 4 LO...

Page 16: ...self checks while displaying Badger Meter DIC Initializing At the end of this cycle its normal mode display will appear In the normal mode if still using the factory defaults Flow Rate will be displa...

Page 17: ...evel Press Enter to view the next set of choices For example pressing Menu from the normal mode screen shows the RESET SETUP DIAG screen Pressing the key brings up the reset screens The key brings up...

Page 18: ...Page 18 6 11 Series 3050 Btu Monitor Page 13 Programming Flow Chart...

Page 19: ...Page 19 6 11 Installation Operation Manual...

Page 20: ...Page 20 6 11 Series 3050 Btu Monitor Page 15...

Page 21: ...Page 21 6 11 Installation Operation Manual Page 16...

Page 22: ...Page 22 6 11 Series 3050 Btu Monitor Page 17...

Page 23: ...Page 23 6 11 Installation Operation Manual Page 18...

Page 24: ...are 2 FTDI Virtual COM port drivers http www ftdichip com FTDrivers htm 3 USB 2 0 A to Mini B 5 pin cable To communicate using HyperTerminal use the following procedure 1 Make sure that the Series 305...

Page 25: ...op bit no parity and no flow control 6 When connected a symbol will appear in theupper left corner of the main HyperTerminal display screen Press the Enter Key Both the Rx and Tx LEDs on the front of...

Page 26: ...9 flow 2 1 total 14 BTU rate 15 BTU total 16 temperature 1 2 17 temperature 1 2 display urate 0 1 10 set the update rate of the display in seconds FLOW INPUT CHANNEL CONFIGURATION flow 1 2 sensor type...

Page 27: ...on relay 5 is the pulse output 0 Totalizer 1 Alarm 2 Manual Control relay 1 5 input 0 8 relay input depends on source for totalizer 0 Flow 1 Total for alarms 0 Flow 1 Rate relay 1 5 units 0 19 units o...

Page 28: ...5 Pulse out rate exceeded 20 Error reading EEPROM on faceplate 21 Error writing EEPROM 22 Analog Input card missing 24 Temperature Input card missing 25 Invalid flow units configured 26 Invalid volum...

Page 29: ...ount 4 80 W x 4 72 H x 3 63 D 120mm x 120mm x 92mm Weight panel mount 12 oz Pulse and Relays Both pulse and relay are fully functional as either totalizing or Set Point outputs Pulse Electrical 1 Amp...

Page 30: ...Page 30 6 11 Series 3050 Btu Monitor Intentionally blank page...

Page 31: ...Page 31 6 11 Installation Operation Manual Intentionally blank page...

Page 32: ...tive entities Copyright 2011 Badger Meter Inc All rights reserved Due to continuous research product improvements and enhancements Badger Meter reserves the right to change product or system specifica...

Reviews: