Page 14
6-11
Series 3050 Btu Monitor
OUTPUT OPTION CARD
If the Series 3050 Btu Monitor was ordered with the Output Option card, it will have several additional outputs.
1.
Analog Output
( 0-20mA; or 4-20mA ) which can be converted externally to 0-5VDC, 1-5VDC with a 250 Ohm resistor; or
0-10VDC or 2-10VDC with a500 Ohm resistor. A 15VDC power supply is provided to permit current sinking or sourcing. The
Series 3050 has special software that permits the Analog output.
2.
USB
for direct access to a computer using a standard mini-USB cable.
3.
RS-485
for fully addressable Modbus or BACnet communication.
1 RS485 B
2 RS485 A
3 RS485 GND
4 LOOP +
5 LOOP -
6 GND
Figure 12: Current Sourcing Analog Output
1 RS485 B
2 RS485 A
3 RS485 GND
4 LOOP +
5 LOOP -
6 GND
Figure 13: Current Sinking Analog Output
Figure 12
RS485 Communication
Figure 13
Use
Standard Cable
USB Type A Male
To
Type Mini B 5 Pin Male
Connect to
Computer USB
Com Port
Model 3700
Model 345WT
or other
MODBUS
Master
Device
Shield
RS485 -
RS485 +
1 RS485 B
2 RS485 A
3 RS485 GND
4 LOOP +
5 LOOP -
6 GND
1 RS485 B
2 RS485 A
3 RS485 GND
4 LOOP +
5 LOOP -
6 GND
Figure 14: RS485 Communication (Modbus and BACnet)
Summary of Contents for Impeller Data Industrial 3050 Series
Page 2: ...Series 3050 Btu Monitor Page ii 6 11...
Page 4: ...Series 3050 Btu Monitor Page iv 6 11...
Page 18: ...Page 18 6 11 Series 3050 Btu Monitor Page 13 Programming Flow Chart...
Page 19: ...Page 19 6 11 Installation Operation Manual...
Page 20: ...Page 20 6 11 Series 3050 Btu Monitor Page 15...
Page 21: ...Page 21 6 11 Installation Operation Manual Page 16...
Page 22: ...Page 22 6 11 Series 3050 Btu Monitor Page 17...
Page 23: ...Page 23 6 11 Installation Operation Manual Page 18...
Page 30: ...Page 30 6 11 Series 3050 Btu Monitor Intentionally blank page...
Page 31: ...Page 31 6 11 Installation Operation Manual Intentionally blank page...