Page 26
6-11
Series 3050 Btu Monitor
USB COMMAND LIST
In the list below, brackets indicate an argument, specifying
its type and value range. For instance [0-18] stands for any
number between 0 and 18 (inclusive).
Example: “display line1 = 1” sets Line 1 of the display to display
#1, which happens to be the totalizer for flow channel 1.
Diagnostics:
id – show model number & software version
echo [on/off] – turn on/off interactive command line:
with echo off, this interface is more
amenable to scripting; it still accepts the
same commands.
Any command entered without an “ = “ sign and
variable will display the current setting.
Example: Typing “display line1” returns “0” which is the
variable for Flow rate.
read flow [1-2] – read the current flow on channel 1 or 2
in GPM.
read flow [1-2] total – read the current total flow on
channel 1 or 2 in gallons.
DISPLAY CONFIGURATION
display line1 = [0-18] – set line 1 of the display
display line2 = [0-18] – set line 2 of the display
valid options are:
0: flow 1 rate
1: flow 1 total
2: flow 2 rate
3: flow 2 total
4: flow 1+2 rate
5: flow 1+2 total
6: flow 1-2 rate
7: flow 1-2 total
8: flow 2-1 rate
9: flow 2-1 total
14: BTU rate
15: BTU total
16: temperature 1&2
17: temperature 1-2
display urate = [0.1-10] – set the update rate of the display, in
seconds
FLOW INPUT CHANNEL CONFIGURATION
flow [1-2] sensor type = [0-4] – flow sensor type:
0: PulseDI,
1: PulseKFactor,
2: PullupKFactor
3: Analog
flow [1-2] sensor dical k = [x] – DI-type flow sensor k
flow [1-2] sensor dical off = [x] – DI-type flow sensor offset
flow [1-2] sensor kfact = [x] – K factor for non-DI sensors
flow [1-2] sensor analog units = [0-19] – flow units for analog
input
flow [1-2] sensor analog range = [0-4] – current range for
analog input
flow [1-2] sensor analog high = [x] – flow rate @max current
flow [1-2] sensor analog low = [x] – flow rate @min current
flow [1-2] sensor avg = [0-100] – averaging "time constant," in
seconds:
flow [1-2] rate units = [0-19] – flow (channel) rate units to
display.
0: GPM
1: gal/s
2: gal/hr
3: Mgal/day
4: L/s
5: LPM
6: L/hr
7: ft3/s
8: ft3/min
9: ft3/hr
10: m3/s
11: m3/min
12: m3/hr
13: acreft/s
14: acreft/min
15: acreft/hr
16: bbl/s
17: bbl/min
18: bbl/hr
19: Custom
flow [1-2] rate ndigits = [2-10] – number of decimal places to
show for flow rate
flow [1-2] rate custom label = [string] – set the label for custom
units
flow [1-2] rate custom conv = [0-100] – conversion factor for
custom units
flow [1-2] total units = [0-7] – set the totalizer units to display
0: gal
1: Mgal
2: L
3: ft3
4: m3
5: acreft
6: bbl
7: Custom
Summary of Contents for Impeller Data Industrial 3050 Series
Page 2: ...Series 3050 Btu Monitor Page ii 6 11...
Page 4: ...Series 3050 Btu Monitor Page iv 6 11...
Page 18: ...Page 18 6 11 Series 3050 Btu Monitor Page 13 Programming Flow Chart...
Page 19: ...Page 19 6 11 Installation Operation Manual...
Page 20: ...Page 20 6 11 Series 3050 Btu Monitor Page 15...
Page 21: ...Page 21 6 11 Installation Operation Manual Page 16...
Page 22: ...Page 22 6 11 Series 3050 Btu Monitor Page 17...
Page 23: ...Page 23 6 11 Installation Operation Manual Page 18...
Page 30: ...Page 30 6 11 Series 3050 Btu Monitor Intentionally blank page...
Page 31: ...Page 31 6 11 Installation Operation Manual Intentionally blank page...