Batch Controller Model CB-30
Page 10
April 2017
CTL-UM-01028-EN-03
Oemote Control Connections
For operator convenience and process automation the functions START, HOLD, RESET and MANUAL can be wired to be used
with remote mounted switches or with electronic control processors Always use shielded wire to protect the signal from
external noise interference
Control Inputs
Remote start, reset, hold, manual, keyboard lockout
Frequency
DC to 20 Hz typical
Type
Current sinking
Logic
Level sensitive
Low Level
0…2V DC max
High Level
8…20V DC max
Impedance
4 7 K
W
pullup to +12V DC
Current
2 5 mA steady state
Oesponse
32 ms make and break time
Table 5: Remote Control Specifications
USE SHIELDED CABLE
SHEILD TO TERM 8
MANUAL
HOLD
START
RESET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
25 26
21 22 23
BADGER METER
MODEL CB-30
Figure 5: Remote Control Connections