background image

7

© Copyright 2012 Badger Fire Protection

Annual Maintenance & Service Examination Procedures

Per NFPA 10, maintenance is a thorough examination of a fire extinguisher and is intended to  
provide maximum assurance that it will operate effectively and safely  It includes a thorough  
examination of all components and the repair or replacement of such items, if necessary 

Maintenance should be performed at intervals not to exceed one year apart or any time an  
inspection discrepancy dictates 

Badger recommends that only authorized Badger distributors and certified personnel who have 
been properly trained to recognize and correct discrepancies, as well as understand all the proper 
industry safety procedures, conduct the maintenance or service of Badger fire extinguishers  Refer 
to the trouble shooting section of this manual for additional information on specific equipment 
observations or discrepancies  

Only Badger factory replacement parts are recommended for 

use in Badger extinguishers.

WARNING:
Prior to servicing or recharging an extinguisher, personnel should be thoroughly  
familiar with the contents of this manual to recognize any equipment conditions or  
discrepancies that might dictate or prohibit further equipment maintenance or repair.

WARNING:
To prevent injury or death, always ensure all pressure is properly relieved from an  
extinguisher prior to attempting any service, repair or recharge.

1   Ensure extinguisher is installed in its proper location and that it is readily accessible  (Badger car-

bon dioxide extinguisher models are approved for temperatures indicated on the nameplate) 

2   Externally examine unit and cylinder for any signs of damage, dents or corrosion that might 

prohibit service or dictate the need for any special maintenance/repair procedures

  Ensure cylindar 

hydro date is within 5 year requirements 

3   Closely examine the extinguisher frame for any damage, corrosion, cracks or deformation    

 

When  the extinguisher is tilted on its wheeled axis, service personnel should listen for any  
 sounds from within the cylinder that might indicate a broken siphon tube or foreign mate-
rial  (Refer to Trouble Shooting section)

4   Examine both wheels to ensure they are secure, not damaged and rotate freely   Lubricate  

as necessary 

5   Unthread and remove the discharge hose assembly from the cylinder valve assembly  Fully extend  

the hose assembly and closely examine the discharge nozzle valve, horn, hose and couplings for  

 

any damage,  abrasions, cracking, thread wear or conditions that might affect its proper function 

 
   (ON Badger CD-100-1 MODELS) – The agent discharge hose assembly and hose manifold  

 assembly must both be disconnected and thoroughly examined 

6   Examine the discharge nozzle valve for any damage or corrosion and while pointing nozzle in a 

safe direction slowly squeeze the lever to verify it operates properly   Ensure the nozzle discharge 
horn is not damaged, cracked or obstructed and is correct for the model 

7  Blow (low pressure) dry air through the discharge hose assembly and nozzle to ensure it is not  

 

plugged or obstructed and operates freely  (If hose is obstructed, properly secure hose assembly  
and using the proper service kit adaptor, connect a regulated pressure source set no higher than 
100 PSI to assist in clearing the hose and nozzle assembly )

Summary of Contents for CD50

Page 1: ...Service Manual Self Expellling Carbon Dioxide Wheeled Fire Extinguishers Models CD50 CD50 1 CD100 CD100 1...

Page 2: ...arts Diagram Page 14 Part Numbers and Description Page 15 Warning Failure to follow the instructions contained herein may result in property damage and or personal injury Important Notice Any time an...

Page 3: ...r cylinders for example is amply covered in NFPA 10 and CFR 49 part 180 209 which reference procedures in CGA pamphlets C 1 C 2 and C 6A NFPA Government Printing Office Compressed Gas Association 1 Ba...

Page 4: ...ersonnel who understand how to properly remove the associated packaging and how to properly prepare the wheeled fire extin guisher for use and fire protection service attempt to do so 1 Examine wheele...

Page 5: ...hich might hinder the flow of agent during fire fighting 6 Operators should approach the fire from upwind to within approximately 10 15 feet of the front edge of the fire 6 Operators should approach t...

Page 6: ...0 day intervals When circumstances require more frequent intervals may be necessary Any time an inspection reveals a discrepancy maintenance and service procedures should be performed 1 Ensure the ext...

Page 7: ...are approved for temperatures indicated on the nameplate 2 Externally examine unit and cylinder for any signs of damage dents or corrosion that might prohibit service or dictate the need for any speci...

Page 8: ...transportation then re install and properly secure the agent cylinder into the carriage frame Ensure the cylinder orientation correctly faces the nameplate operating instructions outward 15 Remove cy...

Page 9: ...charge or further service of the equipment WARNING To avoid personal injury or death always ensure all pressure is properly relieved from an extinguisher prior to attempting any service repair or rech...

Page 10: ...ually examine the cylinder valve discharge port for any signs of thread wear corrosion obstructions or accumulations of any foreign material Ensure the anti recoil device is properly installed 10 Exam...

Page 11: ...obstructed properly secure hose assembly and using the proper service kit adaptor connect a regulated pressure source set no higher than 100 PSI to assist with clearing hose assembly 20 Ensure the dis...

Page 12: ...ny damage or contamination prior to installation of new assemblies Extinguisher cylinders should be replaced any time the pressure vessel has been weakened due to cor rosion cuts dents digs etc and be...

Page 13: ...der outside tolerance De pressurize and recharge Operating instructions missing or illegible Replace Agent cylinder burned or repaired Replace Agent cylinder damaged or corroded Inspect hydrostatic re...

Page 14: ...14 Copyright 2012 Badger Fire Protection Extinguisher Parts Diagram Badger Carbon Dioxide Wheeled Extinguishers CD50 CD50 1 CD100 and CD100 1...

Page 15: ...ain 9 22776 chain drive pin 10 24643 safety relief assembly nut disc and washer 11 22776 siphon tube assembly 12 13735 replacement non flammable gas label 13 22785 replacemtn UN 1013 label 14 22873 Re...

Page 16: ...Badger Fire Protection 944 Glenwood Station Lane Suite 303 Charlottesville Virginia 22911 www badgerfire com Phone 1 800 964 3200 Manual BP84A P N 24645 Rev 07 12 Copyright 2012...

Reviews: