4.5 Cables 

 

Install the supply cables and control cables in separate cable channels. 

Supply voltage 

A cable cross-section of 2.5 mm

2

 and a cable length of 

 5 m is recommended. 

When using stranded wires, the ends must be fitted with ferrules. 
The used connection cable must have a dielectric strength of 

 300 V. 

For small cable lengths, it is also possible to use cable with a cross-section of 

 1.5 mm

2

Copper wires must be used for connection cable with a temperature range of  
-30 °C to +80 °C. 
Further information: 

 

 Table 19 ''Ambient conditions IPC312'', Page  OI

-

42

 

Summary of Contents for IPC312

Page 1: ...Operating instructions IPC312 Version 05 Status September 07 2010 Translation of the original operating instructions...

Page 2: ...tee in regard to the selection specification and or usability of these goods and services The naming and or representation of trademarks which are not owned by Bachmann electronic GmbH are for informa...

Page 3: ...ard OI 16 3 3 Display module OI 18 3 3 1 Technical data OI 18 3 4 Front panel module OI 19 4 Installation OI 21 4 1 Transport storage unpacking OI 21 4 2 Installation notes OI 22 4 3 Installing the de...

Page 4: ...V05 September 07 2010 7 Technical data and dimensional drawings OI 39 7 1 Interference resistance UL approval OI 39 7 1 1 CE compliance OI 39 7 1 2 UL approval OI 40 7 2 Technical data OI 41 7 3 Dimen...

Page 5: ...re and software These warnings are structured as follows WARNING Type and source of danger Potential consequence s if disregarded Measure s to prevent danger Result of the measure s Symbols and terms...

Page 6: ...D BA 0000255 6 3 Structure of safety and warning notices Operating instructions OI 2 V05 September 07 2010...

Page 7: ...al injury or material damage Unauthorized opening and incorrect repairs may result in defective devices or cause malfunctions that may cause danger to the user in connection with connected peripheral...

Page 8: ...C from 01 2010 2006 42 EC Machine Directive EN 60204 must be adhered to The technical specifications and information about conditions for connection are stated on the type plate and in the documentati...

Page 9: ...The extinguishing of the operating LED and other status indicators does not indicate that the device is disconnected from power and is de energized 2 6 CE Directives Bachmann electronic GmbH calls att...

Page 10: ...protected against ESD Unassembled ESDS devices particularly the interior parts e g the mother board can be damaged on contact due to ESD During the handling of these ESDS devices e g during assembly...

Page 11: ...rom Bachmann electronic GmbH in this device provides a high degree of reliability and flexibility with a variety of application possibilities The device can be used in an individual control system but...

Page 12: ...ration system description Operating instructions OI 8 V05 September 07 2010 Fig 3 Device configuration IPC312 1 CF card slot 2 CPU module 3 Interfaces COM 1 2x USB PS 2 2x Ethernet Hex rotary switches...

Page 13: ...r number IPC312 Page OI 41 Model Product name Type Equipment Table 16 Device equipment Order number IPC312 Page OI 41 Supply Supply voltage power consumption SN Serial number Fig 4 Type plate example...

Page 14: ...dule has an integrated power supply unit 3 2 1 Equipment Description Specification Processor AMD Geode LX800 RAM 512 MB DDR SDRAM Drives 1 x CF TYPE I 4 GB 2 x Ethernet 10 100Mbit s 2 x USB 1 1 1 x CO...

Page 15: ...ation system description V05 September 07 2010 OI 11 3 2 2 Interfaces Fig 6 Interfaces IPC3 1 Serial interface COM 1 2 USB interfaces 3 PS 2 interface 4 Ethernet interfaces 5 Hex rotary switches Chapt...

Page 16: ...terface COM 1 RS232 The interface is provided as a complete RS232C D Sub 9 pin male Pin Signal Description 1 DCD Data Carrier Detect 2 RxD Receive Data 3 TxD Transmit Data 4 DTR Data terminal ready 5...

Page 17: ...ification 1 1 Low Speed 1 5 Mbit s Full Speed 12 Mbit s Use only devices that comply with USB Specification 1 1 and that will work with USB 1 1 USB Pin Signal Description 1 5 VDC 5 VDC 2 D Data 3 D Da...

Page 18: ...5 Pin Signal Description 1 TxD Transmit Data 2 TxD Transmit Data 3 RxD Receive Data 4 5 n c not connected 6 RxD Receive Data 7 8 n c not connected Tab 6 Pin assignment for Ethernet socket LED Status D...

Page 19: ...Nibble Tab 8 Hex rotary switches H L 3 2 2 6 Power supply The connector for the supply voltage must be tightened with a torque of 0 5 to 0 6 Nm UL508 5 to 7 in lbs A 2 pin connector is provided for th...

Page 20: ...CF card and the CF card slot of the device are mechanically coded so that the CF card cannot be inserted in the wrong way The card can be used either in the CF card drive of a PC Laptop or directly in...

Page 21: ...Requirements Replacing the CF card requires a Phillips screwdriver No 2 Procedure 1 Loosen the screws 3 2 Turn the protective cover 2 to the side 3 Pull the card 1 out toward the top 4 Insert the new...

Page 22: ...ssible This setting may be entered under Windows system control energy options Operating displays based on TFT technology in continuous in operation and with no or little content change may cause so c...

Page 23: ...D BA 0000304 14 5 Operating instructions Device configuration system description V05 September 07 2010 OI 19 3 4 Front panel module Fig 8 Front panel IPC312 1 Front panel 2 Display module...

Page 24: ...D BA 0000304 14 5 Device configuration system description Operating instructions OI 20 V05 September 07 2010...

Page 25: ...in temperature make sure that no moisture condensation gets on or inside the device Before initial operation the device must be completely dry For this reason an acclimatization period of at least tw...

Page 26: ...ial thickness at the installation cutout should be 2 mm Chapter 7 3 Dimensional drawings Page OI 44 For optimum interference protection the device should be fixed to the place of installation The fron...

Page 27: ...3 4 3 Installing the device Installation in switch cabinet Procedure 1 Fit the device into the cut out from the front 2 Insert the tensioning clamps in the device and fasten them 3 Fix the tensioning...

Page 28: ...A low impedance connection to the ground reduces the danger of an electrical surge in the event of a short circuit or defects in the system Moreover correct grounding and shielding of the cables redu...

Page 29: ...nd a cable length of 5 m is recommended When using stranded wires the ends must be fitted with ferrules The used connection cable must have a dielectric strength of 300 V For small cable lengths it is...

Page 30: ...as they can easily be damaged through mechanical stress which would reduce the shielding effect Grounding cable shields Optimum interference suppression in the high frequency range can be achieved by...

Page 31: ...t both ends with parts of the system grounded in different ways The cause for potential differences may be different mains feeds Potential equalization cable By providing the potential equalization ca...

Page 32: ...D BA 0000305 4 10 Installation Operating instructions OI 28 V05 September 07 2010...

Page 33: ...Starting The device does not have its own power switch Procedure 1 Switch on the system or 2 Connected the device to the supply voltage The device will start up in a predefined state which means the...

Page 34: ...D BA 0000306 14 2 Getting started Operating instructions OI 30 V05 September 07 2010...

Page 35: ...lization hardware make sure that the corresponding resolution has been set 6 1 1 Default settings All required settings for the device factory settings are stored in the default settings A change of t...

Page 36: ...ocedure 1 Press Key Del during the boot up process The setup user interface is opened 2 Select the Device Configuration menu 3 Confirm with key Enter 4 Select the Graphics Configuration menu 5 Confirm...

Page 37: ...D BA 0000307 7 7 Operating instructions Operation and service V05 September 07 2010 OI 33 6 2 Status indication The device is not provided with any status indication such as LEDs...

Page 38: ...4 97 0 Fax 43 0 55 22 34 97 102 E Mail service bachmann info Device does not start no picture Symptom Cause Help Supply voltage not connected or does not exist Check power cable Check pin assignment p...

Page 39: ...tom Cause Help Touchscreen driver software not calibrated Calibrate the touchscreen Inputs are transferred incorrectly Duratouch is detected Display electrically defective Return to manufacturer for r...

Page 40: ...ol Acetaldehyde aliphatic hydrocarbons petrol toluene xylol benzene Acetone methyl ethyl ketone dioxan Chlorofluorocarbons perchlorethylene 1 1 1 trichlorethene trichlorethylene ethylacetat diethyl et...

Page 41: ...so that an exact time of occurrence cannot be specified Reconditioning This effect can be reversed in the long term by displaying a white image for a longer time or changing the background color of t...

Page 42: ...device from the supply voltage 3 Remove all cables devices e g Ethernet keyboard 4 Remove the device Storage Use the original packaging for storage and take into account the climatic conditions Table...

Page 43: ...0 4 2 Level 1 3 No malfunction or permanent impairment on the housing and all interfaces Tested according to EN61000 4 3 HF field AM modulated 80 MHz to 1 GHz 10 V m Interference resistance against hi...

Page 44: ...rican and Canadian market To keep the UL508 each M VIS device must be provided with a UL Listed Class 2 power Supply UL508 UL508 UL Standard for Safety for Industrial Control Equipment UL508C UL508C U...

Page 45: ...perating system Microsoft Windows XP Professional for Embedded Systems Tab 17 Operating system IPC312 Supply voltage Nominal voltage 24 VDC SELV Input voltage range 18 to 36 VDC Power consumption 30 W...

Page 46: ...thout exposing the device to any heat radiation Storage temperature 20 to 60 C Tested according to EN60068 2 2 test Bb and EN60068 2 1 test Ab Relative humidity 5 to 95 without condensation Tested acc...

Page 47: ...45 angle Horizontal IPC312 0 to 50 C 0 to 45 C 0 to 45 C 0 to 45 C Tab 20 Operating temperature IPC312 Cabinet installation Device type Vertical Horizontal IPC312 0 to 45 C 0 to 40 C The operating tem...

Page 48: ...tructions OI 44 V05 September 07 2010 7 3 Dimensional drawings Fig 10 Dimensions IPC312 Dimension mm Weight A Width 337 B Height 256 Depth 97 C Width 321 D Height 233 E Offset outline cut out 8 5 F Of...

Reviews: