1100-2294 Rev 1
14
Network Creating Notes:
To mark devices to be on the same floor, those devices must have the same
floor name (capitalization matters). The MVR-
SC will display a new “floor” tile for
each unique name appearing in the floorplan spreadsheet, up to 16 district
values.
The floor and room cells can be named with any combination of up to eight digits
of letters and/or numbers.
It is possible to hardwire up to 15 devices to the controller
’s Modbus RTU port.
To indicate these in the floorplan, fill in the cells at the bottom of the spreadsheet
(rows with IP m
arked “Direct”).
Each Gateway
’s IP Address must be unique. If only one gateway is used, its IP
address should be 192.168.0.1. The IP address for subsequent gateways would
be 192.168.0.2, 192.168.0.3, etc.
The 7th gateway, if used, has a limit of 10 devices. All other gateways have a
limit of 15 devices.
Figure 8
– Small Example Network