Expected Refrigerant:
Refrigerant analyzed and found to be within an acceptable composition range of the selected
gas will define the results as that refrigerant and display a green screen
(Figure 14)
. In this
example, R-410A is confirmed with some slight composition shift. The R-410A is still within
composition specification of AHRI Standard 700 which qualifies it as R-410A.
Imbalanced Refrigerant:
Refrigerant analyzed and found to have the required components but outside the AHRI
Standard 700 acceptable range will display as Imbalanced with a yellow screen
(Figure 15)
.
In this example, Imbalanced R-410A is confirmed with composition shift. The R-410A has the
correct components but is too far outside the acceptable range to be considered ideal.
Contaminated Refrigerant:
Refrigerant analyzed and found to be contaminated has the expected base components, but
some other refrigerant(s) is present diluting the entire sample. This refrigerant would have a
red screen to indicate it is unacceptable and should not be recovered with pure gas or
reused
(Figure 16)
. In this example, Imbalanced R-410A is contaminated with R-22.