GDA-1600 16-Channel Controller
Instruction 5700-9001
10
3 Operation
The GDA-1600 offers 3 graphic screens for viewing monitored data and a
Set-Up
menu
screen for operator interface to configuration menus. They are shown below in Figure
3.0. The
Bar Graphs
screen allows viewing of all active channels simultaneously. The
Trend
screen displays a 24 hour trend, one channel at a time. The
Combination
screen
displays a bar graph, large engineering units and a 30 minute trend, one channel at a time.
Input channels may be displayed in sequence with the
UP/DOWN
keys. The
NEXT
key
switches between the 3 graphic data screens. When power is applied to the GDA-1600,
the graphic LCD returns to the last active screen from when power was removed.
Setup
menus are entered by pressing
EDIT
from any data screen, and scrolling to the
desired menu using the
UP/DOWN
keys. Pressing
EDIT
again enters the selected
menu’s tree of variables. This
Setup
mode may be exited manually by pressing
NEXT,
or automatically when no keys are pressed for 5 minutes. Alarm relays and front panel
alarm LED indicators remain active during the
Setup
mode. An
AUTHORIZE
menu
offers a password feature to prevent tampering with GDA-1600 parameters.
Figure 3
.0
– Setup Menus
3.1
Setup Menu Configuration
Variables inside
system
and
channel
menu trees allow optimum GDA-1600 configuration
for a wide range of demanding multi-point monitoring applications. Access to menus are
accomplished via the
Setup
mode by pressing
EDIT
and activating the
Setup
screen
shown in Figure 3.0. Menu trees are provided for each of the 16 channels and another for
system variables. Select the desired menu by scrolling with
UP/DOWN
and
EDIT
to
enter the menus.
Summary of Contents for GDA-1600
Page 21: ...Instruction 5700 9001 GDA 1600 16 Channel Controller 21 Figure 3 10 Configuration Menus ...
Page 28: ...GDA 1600 16 Channel Controller Instruction 5700 9001 28 Figure 4 2 Main PCB ...
Page 36: ...GDA 1600 16 Channel Controller Instruction 5700 9001 36 Figure 4 7 Analog Output Board ...
Page 38: ...GDA 1600 16 Channel Controller Instruction 5700 9001 38 Figure 5 2 System Diagnostic Options ...
Page 53: ...Instruction 5700 9001 GDA 1600 16 Channel Controller 53 ...