Instruction 5700-9001
GDA-1600 16-Channel Controller
23
Entries
Description
Acknowledge Turning
Acknowledge
ON
(not available on Alarm 1) allows the common relay to be
deactivated during alarm conditions by an
Alarm Reset
. This is useful if an audible
device is being driven by the relay.
All relays are rated at 5 Amp for 28 VDC and 250 ~VAC
RESISTIVE
loads.
IMPORTANT:
Appropriate diode (DC loads) or MOV (AC loads)
snubber devices must be installed with inductive loads to prevent RFI
noise spikes. Relay wiring should be kept separate from low level signal
wiring.
3.3.2
Discrete Relay “Failsafe” Mode
Discrete relay options (P/N 5700-0012) may also be configured to function in a
Failsafe
mode using the System Setup menu shown in Figure 3.12. Entering YES causes these
discrete relays to have energized coils when no alarm condition exists for the associated
channel and de-energized coils when the alarm occurs.
Failsafe
is useful for indicating
failed relay coils and loss of power conditions.
IMPORTANT:
Zoning jumpers (P/N 5700-0012) as seen in Figure
4.4 should not be used when Discrete Relays menus are set for
failsafe.
Zoning jumpers cause ANY relay in the zone to energize ALL
other relays in the same zone. Zoning of failsafe relays may be
accomplished with wiring at the relay contact terminals.
Figure
3.12
– Failsafe Mode
3.3.3
Common Horn Relay
&
Local Piezo
The GDA-1600 is equipped with a low decibel audible piezo which chirps when keys are
pressed and may be configured to audibly indicate alarm conditions. The common horn
relay is similar to the common A1 & A2 common relays.
Figure
3.13
– Common Horn / Local Piezo Options
Summary of Contents for GDA-1600
Page 21: ...Instruction 5700 9001 GDA 1600 16 Channel Controller 21 Figure 3 10 Configuration Menus ...
Page 28: ...GDA 1600 16 Channel Controller Instruction 5700 9001 28 Figure 4 2 Main PCB ...
Page 36: ...GDA 1600 16 Channel Controller Instruction 5700 9001 36 Figure 4 7 Analog Output Board ...
Page 38: ...GDA 1600 16 Channel Controller Instruction 5700 9001 38 Figure 5 2 System Diagnostic Options ...
Page 53: ...Instruction 5700 9001 GDA 1600 16 Channel Controller 53 ...