HP2
Shallow Housing - Standard MR16 & PAR36/AR111
Remote Transformer Installation
Housing Installation
This product is intended for use
ONLY in areas of restricted depth.
Designer should detail the
following warning in all
specifications documents:
WARNING
MANDATORY:
Installer
MUST
use water-tight fittings and ensure
a sealed conduit/wiring system or
this fixture will leak. Failure to do
so will
VOID WARRANTY.
Installer To Provide DRY
CONDUIT SYSTEM
5.
For concrete installation:
Fill the hole around
the fixture housing to 12” below the finished
grade with clean fill dirt and tamp carefully to
prevent settling of fixture. Pour concrete and
finish as required flush with the top surface of
the temporary cover.
Under no circumstances should the
faceplate be below grade after installation.
3. Per DIG-IT Guide, backfill the gap between
the bottom of housing and bottom of hole with
sand for drainage.
4.
For soil installation:
Fill and tamp soil to
the appropriate height leaving room for sod,
pavers, etc. to be level with the top of the
faceplate.
Under no circumstances should the
faceplate be below grade after installation.
Soil installation is not drive-over rated.
2. Place housing in excavated hole. Align power
cord with leads in the path of the conduit
trench(es).
1. Secondary wiring is pre-wired with 5’ leads.
Pull 5’ secondary leads from shallow HP2
housing though 3/4” conduit. Make watertight
connections to secondary side of remote
transformer using waterproof wire connectors
in a waterproof splice compartment (not
included) as per NEC.