LED function indicators after each mains recovery (60 sec. initialisation period)
Operating state
LED function indicators
Factory pro-
gram active
White, red and green flash in quick succession for 10 sec., then initialisation indicators,
see below
Double-locked
white and green shines for 5 sec. all 20 sec., afterwards initialising notification
Indicator
unprogrammed
Indicator
programmed
Indicator also when forced shutdown
is activated
Standard mode
Red flashes
Red flashes quickly
Every 5 sec., 4 x white, red and
green in quick succession
12 h ON/OFF
active
Red and green
flash
Red and green flash
quickly
Every 5 sec., 4 x white, red and
green in quick succession
Corridor active
Red and white
flash
Red and white flash
quickly
Every 5 sec., 4 x white, red and
green in quick succession
12 h ON/OFF
& corridor active
Red, green and
white flash
Red, green and white
flash quickly
Every 5 sec., 4 x white, red and
green in quick succession
CdS active
–
Red and white flash
Then no red LED for motion detection
LED function indicators during operation
Process
LED function indicators
Motion detection
Red flashes on each detected movement
Semi-automatic
mode active
White is ON
Impulse active
red and green flash one time all 4 sec.
Corridor active
White ON 1 sec. and OFF 4 sec.
Corridor and
semi-automatic mode
active
White ON 4 sec. and OFF 1 sec.
Too bright detected
Green flashes
Light measurement
active
Green flashes once every 10 sec.
12 h ON/OFF
function active
Red and green flash alternately
Duration ON active
(by slave)
Red flashes quickly
IR command
White flashes once
IR command „Open“
and sabotage active White and green flash once slowly
1 2 3
1 2 3
Sensor and power supply in one case
Power supply:
11-48 VAC/DC
Power consumption:
< 1W
Ambient temperature:
-25°C to +50°C
Degree of protection/class:
AP IP20 wit accessory socket
IP54, FC IP20 / II
Settings:
Potentiometer, DIP-switch and
by remote control
Light values – IR-PD-2C:
10 - 2000 Lux
Extension of the detection area:
with PD2-M-2C-11-48V-RR
Area of coverage:
circular 360°
Range of coverage Ø H 2,50 m / T = 18°C:
seated 4 m / tangential 10 m / radial 6 m
Recommended height for mounting:
2 - 3 m
Light measurement:
mixed light, da artifi-
cial light
Light values potentiometer:
10 - 2000 Lux
• Channel 1 and 2:
each a potential-free contact
NO
Contact load:
Version 3A
11-48VAC/DC, 3 A cos φ=1
Version RR with Reed-relay 11-48VAC/DC, 100 mA for
extra
low-noise switching, cos φ=1
Time settings (Channel 1):
15 sec. - 16 min. (30 min.
with remote control) / Test
Time settings (Channel 2):
alarm-impulse with 3 impulses
per 10 sec.
Dimensions H x Ø [mm]
SM
FC
PD2-M-2C-11-48V
50 x 98 84.5 x 80
Visible portion when built into ceiling:
34 x 79 mm
Declaration of Conformity:
The product complies
with the low voltage recommendation 2006/95/EC and
the EMV recommendation 2004/108/EC.
19. Technical data PD2-Master-2C-11-48V
22b. PD2-M-2C-11-48V-FC – Connections
23. LED function displays
22a. PD2-M-2C-11-48V-SM – Connections
M
A
N 7
34
5
–2
70
11
4–2
20. Article / Part nr. / Accessory
21. Wiring diagram
Standard operation with Master-2 channels-11-48 V-detector
Light sensor operation with Master-2 channel-11-48V-
occupancy detector with Reed-relay
Wiring diagram for
• PD2-M-2C-11-48V-3A
• PD2-M-2C-11-48V-RR
Wiring diagram for
• PD2-M-2C-11-48V-RR
X1 = light sensor
Optional
T1 = T1 = NO button for semi-automatic mode
As Slave please use PD2-M-2C-11-48V-RR!
C2 in the pulse mode
Typ
SM
FC
PD2-M-2C-11-48V-3A
92154
92164
PD2-M-2C-11-48V-RR
92305
92306
LUXOMAT
®
Remote control:
IR-PD
92160
IR-PD-2C (incl. wall bracket)
92475
Accessory:
BSK Ball basket guard
92199
~/+
~/–
R
X1
X2
Slave
11-48V
AC/DC
C2
C1
NO
NO
NO
NO
R+ + –
R
T1
~/+
NO
R
~/
~/+
~/+
NO
C1
T1
NO
NO
C2
~/
24V
24V
NO
R
~/
~/+
~/+
NO
C1
NO
NO
C2
24V
24V
24V
AC/DC
X2
X1
1k 15M
1 2 3
12
3
~/+
~/–
R
X1
X2
Slave
11-48V
AC/DC
C2
C1
NO
NO
NO
NO
+
–
R
T1
3 2 1