B.E.G. luxomat PD2-M-2C-11-48V Installation And Operating Instructions Download Page 2

9.   Settings by remote control IR-PD-2C 

10.   Key functions in closed state

Unlocking device - Activation of the programming mode

Locking device - Exit programming mode 

 

Done for about 3min. no further action, will be deactivate  

the programming mode automatically.

Change between fully automatic  

and semi automatic mode (HA)

Luminance set point for channel 1  

20 - 1000 Lux

Automatic reading in the current light value as new 

luminance set point

Change between motion detector and  

photo electric switch

Gradually increase the current light level by  

20 resp 50 Lux

Light ON/OFF

HA

ON/OFF

Light ON/OFF during the detection of motion plus 

follow-up time; 

Activation of the 12 h-ON/OFF-function by holding 

down the push button

Switches channel off and is immediately active again, 

exits all timers, interruption of light measurement

Permanent protection against sabotage  

This function blocks the  

LUXOMAT

®

 PD2-M-2C-11-48V  

permanently. This operating mode can only be 

activated during the period of 5 seconds (white LED 

flash) after pressing the “lock“ button. The procedure 

for leaving this mode is as follows: 

 

 

1. Switch off the current

 

2.  Apply current for 31 - 59 seconds 

 3. 

Switch of the current again

 

4.  Apply current, wait for selftest cycle

 5. 

Open detector

Changes to “open“ state

Resetting when 

open: 

Deletes 

all values set 

with the remote 

control, light OFF. 

Potentiometer 

and DIP switches 

are enabled for 

setting.

or

1000

20

to

+

Follow-up time ch1 (light)  

5  - 30 min. or impulse  
Follow-up time ch2 (HVAC)  

5  - 30 min. resp. 120 min. or impulse 

��

���

to

LED ON/OFF (by holding down the push button)

Activation/Deactivation of the test function

After 3 minutes the test mode will be automatically 

closed.

Confirmation

Detection sensitivity reduced or normal

Daytime operation, detector only activated by motion

or

PI R

CdS

Permanent protection against sabotage

White LED flashes

for c

hoice CdS

max

50

Lux

1500

Lux

ON

OFF

Option: Remote control IR-PD-2C

Wall bracket for remote control  

IR-PD-2C 

An adhesive film for the surface of the IR-PD-2C-S is inclu-

ded with the device. If required, this can be used for any 

B.E.G.

 remote control with 27 keys.

In order to benefit from the whole range of functions of 

the PD2-M-2C-11-48V, please order separately the remote 

control IR-PD-2C.

8.  Putting into operation of the remote 

control IR-PD-2C (optional)

Check Battery:

 

Open battery compartment 

by pressing the plastic springs 

together and removing the 

battery-holder.

 

Caution:

 Settings with remote control supersede  

the settings by potentiometers. 

1

2

120 6050

40

30

15

10

A

16 10

5

2

1

30

15

TEST

2000

1200

600

200

40

5

120 6050

40

30

15

10

A

16 10

5

2

1

30

15

TEST

2000

1200

600

200

40

5

t < 5 s

LUXOMAT

®  

 

PD3

B.E.G.

B.E.G.

LUXOMAT

®

B.E.G.

LUXOMAT

®

500

200

400

100

20

IR-PD-2C-S

ON/OFF

HA

min

30

min

60

min

120

B.E.G.

LUXOMAT

®

R2

R1

R1

Film IR-PD-2C-S

IR-PD-2C - 92475

or

7. Reset and default settings

1. Default settings 

If the potentiometers are in the 

“Test“ and “Sun“ position and the 

detector is unprogrammed, the  

factory program is activated: 

500 Lux and 10 min.

2. Reset 

 

If both potentiometers are returned to the ”Test“ and “Sun“ 

setting from any other position, a reset is executed. All values 

programmed with the remote control are deleted.

��

���

��

���

min

120 

min

min

max

50

Lux

1500

Lux

ON

OFF

t < 5 sec.

optional

optional

optional

optional

optional

optional

Summary of Contents for luxomat PD2-M-2C-11-48V

Page 1: ...re overriden using the remote control 5 DIP Switch functions DIP switch ON OFF 1 Semi automatic mode Fully automatic mode 2 LED OFF LED ON 3 Corridor mode Standard mode Corridor function After deactivation by an external push button the detector switches off and returns to automatic mode after 5 sec The DIP settings are enabled again by Adjusting the DIP switches when closed Reset with test sun se...

Page 2: ...g down the push button Activation Deactivation of the test function After 3 minutes the test mode will be automatically closed Confirmation Detection sensitivity reduced or normal Daytime operation detector only activated by motion or PI R CdS Permanent protection against sabotage White LED flashes for choice CdS max 50 Lux 1500 Lux ON OFF Option Remote control IR PD 2C Wall bracket for remote con...

Page 3: ...orridor function The behaviour when the push button is pressed is defined as follows Corridor function activated Light ON Push button pressed briefly Light OFF Active after 5 sec Push button held down Light OFF Active after 5 sec Light OFF Push button pressed briefly Light ON as long as motion Lag time Push button held down Light ON as long as motion Lag time 14a Behaviour of external push button ...

Page 4: ...ee of protection class AP IP20 wit accessory socket IP54 FC IP20 II Settings Potentiometer DIP switch and by remote control Light values IR PD 2C 10 2000 Lux Extension of the detection area with PD2 M 2C 11 48V RR Area of coverage circular 360 Range of coverage Ø H 2 50 m T 18 C seated 4 m tangential 10 m radial 6 m Recommended height for mounting 2 3 m Light measurement mixed light daylight artif...

Reviews: