Installation and Operating Instruction for
B.E.G.
- occupancy detector PD2-M-2C-11-48V-3A-SM/-FC and PD2-M-2C-11-48V-RR-SM/-FC
LUXOMAT
®
PD2-M-2C-11-48V
1. Mounting preparation
Work on the 230 V mains supply may only be carried out by
qualified professionals or by instructed persons under the direc-
tion and supervision of qualified skilled electrical personnel in
accordance with electrical regulations.
Disconnect supply before installing!
The device is not suited for safe disconnection of the mains
supply.
When in Master/Slave mode of operation, the Master-
appliance must always be installed at the location where there
is least daylight.
EN
2b. Installation LUXOMAT
®
PD2-M-2C-11-48V-FC
A circular opening of diameter
68 mm must first of all be pro-
duced in the ceiling.
Having connected up the cables in accordance with regula-
tions, the detector is inserted into the opening as shown in the
drawing opposite and fixed into position with the assistance
of the spring clip.
The detector must be installed on a solid
and level surface. There is no need for
frames.
For mounting remove lens (turn anticlock-
wise). Fasten the mounting pod to the
ceiling.
Having connected up the wires in accordance with regula-
tions, secure the detector with 2 screws as per the illustration
above. In order to assemble the detector outside, the PD2-IP54
base-plate, which is available as an accessory, must be
mounted between the detector and the surface on which it is
to be installed.
2a. Installation LUXOMAT
®
PD2-M-2C-11-48V-SM
3b. Hardware configuration FC
Position LED’s and potentiometer
LED
1 green
LED
2 white
LED
3 red
Potentiometer 1
Lux Channel 1
Potentiometers 2
Time Channel 1
Potentiometers 3
Time Channel 2
LED
1 green
LED
2 red
LED
3 white
3a. Hardware configuration SM
Position LED’s
DIP 1
Fully automatic/semi automatic mode
DIP 2
LED ON/OFF
DIP 3
Change between corridor mode and standard mode
The DIP switch settings are
overriden
using the remote control.
4a. Position potentiometers and DIP-Switches SM
4b. Position DIP-Switches FC
False ceiling
mounting
DIP 1
Fully automatic/semi automatic mode
DIP 2
LED ON/OFF
DIP 3
Change between corridor mode and standard mode
The DIP switch settings are
overriden
using the remote control.
5. DIP-Switch functions
DIP-
switch
ON
OFF
1
Semi automatic mode
Fully automatic mode
2
LED OFF
LED ON
3
Corridor mode
Standard mode
Corridor function:
After deactivation by an external push
button, the detector switches off and returns to automatic mode
after 5 sec.
The DIP settings are enabled again by:
• Adjusting the DIP switches when closed
• Reset with test sun setting at the potentiometers
• Reset when open
Surface mounting
OFF
ON
VA
LED
HA
COR
ON
OFF
DIP
40
15
30 1 2 5
10
16
TES
T
120
A
5
60
50
40
30
15
x
1
2 3
Potentiometer 3
Time Channel 2
Potentiometer 2
Time Channel 1
Potentiometer 1
Lux Channel 1
DIP
OFF
ON
1 2 3
40
15
30 1 2 5
10
16
TES
T
120
A
5
60
50
40
30
15
x
1 2
3
1
1
2
2 3
3
ON
OFF
DIP
1
2
3
6.
Putting into operation / Settings
Self test cycle
After an initial 60-second self-test cycle, the
LUXOMAT
®
PD2-M-2C-11-48V is ready for operation.
Potentiometer 1 - Adjustment twilight-switch for
channel 1
The switch-on value for the light can be set at
between 10 and 2000 Lux. Using the potenti-
ometer, the luminance set points can be set as
desired.
Symbol
:
Night operation
Symbol :
Day/Night operation
Determining the current brightness
Set potentiometer 2 to the „Test“ setting. The
green LED lights up permanently as soon as
the value set at the potentiometer “Lux” dropps
below the current measured brightness.
Potentiometer 2 - Adjustment follow-up time
channel 1 “Light“
Symbol
TEST
: Test mode, reacts on motion only.
Every movement switches on the light for a pe-
riod of 2 seconds, switching it off for a period
of 2 seconds. The time can be set infinitely vari-
ably at between 15 sec. and 16 minutes.
The potentiometer settings are overriden using the remote
control.
Potentiometer 3 - Follow-up time for appliance-
control
The time can be set infinitely variably at between
5 minutes and 120 minutes. After 15 minutes
the switch-on delay is activated. This is around
5 min. If there are not detected any further
movements within this period, the switch-on delay
starts again.
Symbol :
Impulse = 2.5 sec.
Symbol
A
:
Alarm impulse = 2 sec.
Alarm impulse
In order to set off an alarm impulse, at least 3
movements within 9 sec. have to be detected.
120 6050
40
30
15
10
A
16 10
5
2
1
30
15
TEST
2000
1200
600
200
40
5
120 6050
40
30
15
10
A
16 10
5
2
1
30
15
TEST
2000
1200
600
200
40
5
120 6050
40
30
15
10
A
16 10
5
2
1
30
15
TEST
2000
1200
600
200
40
5