Installation and Operating Instruction for 

B.E.G.

 - occupancy detector PD2-M-2C-11-48V-3A-SM/-FC and PD2-M-2C-11-48V-RR-SM/-FC

LUXOMAT

®

PD2-M-2C-11-48V

 1. Mounting preparation 

 

Work on the 230 V mains supply may only be carried out by 

qualified professionals or by instructed persons under the direc-

tion and supervision of qualified skilled electrical personnel in 

accordance with electrical regulations.

Disconnect supply before installing!

The device is not suited for safe disconnection of the mains 

supply. 

 

When in Master/Slave mode of operation, the Master-

appliance must always be installed at the location where there 

is least daylight.

EN

2b.    Installation  LUXOMAT

®

 PD2-M-2C-11-48V-FC

A circular opening of diameter 

68 mm must first of all be pro-

duced in the ceiling. 

Having connected up the cables in accordance with regula-

tions, the detector is inserted into the opening as shown in the 

drawing opposite and fixed into position with the assistance 

of the spring clip.  

The detector must be installed on a solid 

and level surface. There is no need for 

frames.  

For mounting remove lens (turn anticlock-

wise). Fasten the mounting pod to the 

ceiling.

Having connected up the wires in accordance with regula-

tions, secure the detector with 2 screws as per the illustration 

above. In order to assemble the detector outside, the PD2-IP54 

base-plate, which is available as an accessory, must be 

mounted between the detector and the surface on which it is 

to be installed.

2a.    Installation  LUXOMAT

®

 PD2-M-2C-11-48V-SM

3b.    Hardware configuration FC 

Position LED’s and potentiometer

LED

1 green

LED

2 white 

LED

3 red 

Potentiometer 1

  

Lux Channel 1

Potentiometers 2

 

Time Channel 1 

Potentiometers 3

 

 Time Channel 2

LED

1 green

LED

2 red 

LED

3 white 

3a.  Hardware configuration SM 

Position LED’s

  DIP  1

    

Fully automatic/semi automatic mode

 

DIP 2

  

LED ON/OFF

DIP 3

    

Change between corridor mode and standard mode

 

The DIP switch settings are 

overriden

 using the remote control. 

4a. Position potentiometers and DIP-Switches SM

4b. Position DIP-Switches FC

False ceiling  

mounting

 DIP  1

  

 

Fully automatic/semi automatic mode

 

DIP 2

 

LED ON/OFF

DIP 3

 

 Change between corridor mode and standard mode

 

  

The DIP switch settings are 

overriden

 using the remote control. 

5. DIP-Switch functions

DIP-

switch

ON

OFF

1

Semi automatic mode

 Fully automatic mode

2

LED OFF

 LED ON

3

Corridor mode

 Standard mode

Corridor function:

 After deactivation by an external push 

button, the detector switches off and returns to automatic mode 

after 5 sec.

The DIP settings are enabled again by:
• Adjusting the DIP switches when closed
• Reset with test sun setting at the potentiometers
• Reset when open

Surface mounting

OFF

ON

VA

LED

HA

COR

ON

OFF

DIP

40

15

30 1 2 5

10

16

TES

T

120

A

5

60

50

40

30

15

x

1

2 3

Potentiometer 3

 Time Channel 2 

Potentiometer 2

 Time Channel 1 

Potentiometer 1

 Lux Channel 1

DIP

OFF

ON

1 2 3

40

15

30 1 2 5

10

16

TES

T

120

A

5

60

50

40

30

15

x

1 2

3

1

1

2

2 3

3

ON

OFF

DIP

1

2

3

6. 

Putting into operation / Settings

 

 

Self test cycle 

After an initial 60-second self-test cycle, the 

LUXOMAT

®

  

PD2-M-2C-11-48V is ready for operation. 

Potentiometer 1 - Adjustment twilight-switch for 

channel 1 

The switch-on value for the light can be set at 

between 10 and 2000 Lux. Using the potenti-

ometer, the luminance set points can be set as 

desired.
Symbol

 

Night operation

Symbol  :  

Day/Night operation

Determining the current brightness

 

Set potentiometer 2 to the „Test“ setting. The 

green LED lights up permanently as soon as 

the value set at the potentiometer “Lux” dropps 

below the current measured brightness.  

  Potentiometer 2 - Adjustment follow-up time 

channel 1 “Light“  

Symbol 

TEST

: Test mode, reacts on motion only. 

Every movement switches on the light for a pe-

riod of 2 seconds, switching it off for a period 

of 2 seconds. The time can be set infinitely vari-

ably at between 15 sec. and 16 minutes.

The potentiometer settings are overriden using the remote 

control.

Potentiometer 3 - Follow-up time for appliance-

control  

 

The time can be set infinitely variably at between 

5 minutes and 120 minutes. After 15 minutes 

the switch-on delay is activated. This is around 

5 min. If there are not detected any further 

movements within this period, the switch-on delay 

starts again.
Symbol  : 

Impulse = 2.5 sec. 

Symbol 

A

Alarm impulse = 2 sec.  

Alarm impulse

In order to set off an alarm impulse, at least 3 

movements within 9 sec. have to be detected.

120 6050

40

30

15

10

A

16 10

5

2

1

30

15

TEST

2000

1200

600

200

40

5

120 6050

40

30

15

10

A

16 10

5

2

1

30

15

TEST

2000

1200

600

200

40

5

120 6050

40

30

15

10

A

16 10

5

2

1

30

15

TEST

2000

1200

600

200

40

5

Summary of Contents for luxomat PD2-M-2C-11-48V

Page 1: ...re overriden using the remote control 5 DIP Switch functions DIP switch ON OFF 1 Semi automatic mode Fully automatic mode 2 LED OFF LED ON 3 Corridor mode Standard mode Corridor function After deactivation by an external push button the detector switches off and returns to automatic mode after 5 sec The DIP settings are enabled again by Adjusting the DIP switches when closed Reset with test sun se...

Page 2: ...g down the push button Activation Deactivation of the test function After 3 minutes the test mode will be automatically closed Confirmation Detection sensitivity reduced or normal Daytime operation detector only activated by motion or PI R CdS Permanent protection against sabotage White LED flashes for choice CdS max 50 Lux 1500 Lux ON OFF Option Remote control IR PD 2C Wall bracket for remote con...

Page 3: ...orridor function The behaviour when the push button is pressed is defined as follows Corridor function activated Light ON Push button pressed briefly Light OFF Active after 5 sec Push button held down Light OFF Active after 5 sec Light OFF Push button pressed briefly Light ON as long as motion Lag time Push button held down Light ON as long as motion Lag time 14a Behaviour of external push button ...

Page 4: ...ee of protection class AP IP20 wit accessory socket IP54 FC IP20 II Settings Potentiometer DIP switch and by remote control Light values IR PD 2C 10 2000 Lux Extension of the detection area with PD2 M 2C 11 48V RR Area of coverage circular 360 Range of coverage Ø H 2 50 m T 18 C seated 4 m tangential 10 m radial 6 m Recommended height for mounting 2 3 m Light measurement mixed light daylight artif...

Reviews: