REGISTERS
The logger configurable parameters are organized in a Table of Registers. The block reading command makes possible to read
multiple registers with the same request.
The configuration software, however, makes such table not necessary, once it reads and writes in all registers that require
configuration. Each parameter in the table is a word of 16 bits.
The available Modbus command for the reading operation is the following:
HOLDING
REGISTERS
DESCRIPTION
HOLDING
REGISTERS
DESCRIPTION
0000
Current Value of Channel 1
0101
Bytes 2 and 3 of Channel 5 String (tag)
0001
Current Value of Channel 2
0102
Bytes 4 and 5 of Channel 5 String (tag)
0002
Current Value of Channel 3
0103
Bytes 6 and 7 of Channel 5 String (tag)
0003
Current Value of Channel 4
0104
Bytes 0 and 1 of Channel 6 String (tag)
0004
Current Value of Channel 5
0105
Bytes 2 and 3 of Channel 6 String (tag)
0005
Current Value of Channel 6
0106
Bytes 4 and 5 of Channel 6 String (tag)
0006
Current Value of Channel 7
0107
Bytes 6 and 7 of Channel 6 String (tag)
0007
Current Value of Channel 8
0108
Bytes 0 and 1 of Channel 7 String (tag)
0008
Informs Alarm Status
0109
Bytes 2 and 3 of Channel 7 String (tag)
0009
Reserved: Inform General
Status
0110
Bytes 4 and 5 of Channel 7 String (tag)
0010
Informs Channel 1 and 2 Status
0111
Bytes 6 and 7 of Channel 7 String (tag)
0011
Informs Channel 3 and 4 Status
0112
Bytes 0 and 1 of Channel 8 String (tag)
0012
Informs Channel 5 and 6 Status
0113
Bytes 2 and 3 of Channel 8 String (tag)
0013
Informs Channel 7 and 8 Status
0114
Bytes 4 and 5 of Channel 8 String (tag)
0014
Current Time (seconds and
minute)
0115
Bytes 6 and 7 of Channel 8 String (tag)
0015
Current Time (hour and day)
0116
Bytes 0 and 1 of the Engineering Unit of
Channel 1
0016
Current Time (month and year)
0117
Bytes 2 and 3 of the Engineering Unit of
Channel 1
0017
Channel 1 Configuration
0118
Bytes 4 and 5 of the Engineering Unit of
Channel 1
0018
Channel 2 Configuration
0119
Bytes 6 and 7 of the Engineering Unit of
Channel 1
0019
Channel 3 Configuration
0120
Bytes 0 and 1 of the Engineering Unit of
Channel 2
0020
Channel 4 Configuration
0121
Bytes 2 and 3 of the Engineering Unit of
Channel 2
0021
Channel 5 Configuration
0122
Bytes 4 and 5 of the Engineering Unit of
Channel 2
0022
Channel 6 Configuration
0123
Bytes 6 and 7 of the Engineering Unit of
Channel 2
0023
Channel 7 Configuration
0124
Bytes 0 and 1 of the Engineering Unit of
Channel 3
0024
Channel 8 Configuration
0125
Bytes 2 and 3 of the Engineering Unit of
Channel 3
0076
Bytes 0 and 1 of the Title String
0126
Bytes 4 and 5 of the Engineering Unit of
Channel 3
0077
Bytes 2 and 3 of the Title String
0127
Bytes 6 and 7 of the Engineering Unit of
Channel 3