22
Chapter 3. MOUNTING AND WIRING
• Take care that event output 2 (the open collector output) does not
exceed the output rating of this device. When driving a relay, be
sure to use one with a built-in coil surge absorption diode. Failure
to do so might cause faulty operation.
z
Mounting the operation panel/display
On this device, the operation panel/display can be rotated up to 180°
to an easyto-view position. Follow the procedure below to mount the
operation panel/display:
(1) Connect the connectors of the leads from the operation panel/
display to the sensor/terminal section.
(2) Rotate the display to the most easily visible position.
(3) Fasten the operation panel/display onto the sensor/terminal
section with screws.
CW rotation max. 180°
CCW rotation max. 180˚
Connector leads
Operation panel/
display
Sensor/terminal
section
Combination No. indication
Handling Precautions
• The maximum screw tightening torque is 1.0N•m. The IP54 seal
might be impaired if screws are too tight or too loose.
• Arrange the leads connecting the sensor/terminal section and the
operation panel/display so they are not unnecessarily twisted or
pinched when fitting the sections together.
• Prevent the leads connecting the sensor/terminal section and the
operation panel/display from being damaged.
• Do not rotate the operation panel/display beyond 180° to the
left or right. This section may be rotated to the left or right if it is
mounted upside down.