B-3
INDEX Parameter name
Description
Sub-parameter
name
Access
attribute
Size
(Byte)
Range
Factory default
setting
26
SHED_RCAS
Sets the timeout time for writing the value
for a setting value change (SPC) from the
host arithmetic unit connected with the
RCAS_IN parameter when MODE of the
Function block is RCAS. If the setting
value is not written within this set time,
the Function block automatically transits
to the mode which has been set to the
SHED_OPT parameter in the Function
block.
-
S-R/W
4
0 ≤ X ≤ 0x
FFFFFFFF
640000(20sec)
27
SHED_ROUT
Sets the timeout time for writing the value
for an output value change (DDC) from
the host arithmetic unit connected with
the ROUT_IN parameter when MODE of
the Function block is ROUT. If the setting
value is not written within this set time,
the Function block automatically transits
to the mode which has been set to the
SHED_OPT parameter in the Function
block.
-
S-R/W
4
0 ≤ X ≤ 0x
FFFFFFFF
640000(20sec)
28
FAULT_STATE
Indicates the fail-safe condition.
-
N-R
1
1: Clear
2: Active
1: Clear
29
SET_FSTATE
Starts the fail-safe state.
-
D-R/W
1
1: Off
2: Set
-
30
CLR_FSTATE
Cancels the fail-safe state.
-
D-R/W
1
1: Off
2: Set
-
31
MAX_NOTIFY
The maximum number of alerts to be
retained.
-
S-R
1
3
3
32
LIM_NOTIFY
Limit of the number of alerts. Being set by
the user, the number of alerts to be notified
to the host can be limited to prevent
overflow of the host.
-
S-R/W
1
0 ≤ X ≤ 3
3
33
CONFIRM_TIME
Parameter for setting the wait time for
confirmation of an alert.
-
S-R/W
4
0 ≤ X ≤ 0x
FFFFFFFF
640000(20sec)
34
WRITE_LOCK
Prohibits setting values from being written
from outside.
-
S-R/W
1
1: Unlocked
2: Locked
1: Unlocked
35
UPDATE_EVT
Parameter for generating an alert when
fixed data (data whose access attribute is
“S-”) of the Resource block is changed. The
configuration is as follows:
· Unacknowledged: Determined state
· Update_State: Change state
· Time_stamp: Change time
· Static_Revision: Revision after change
· Relative_Index: Changed parameter
identification number
Unacknowledged D-R/W
1
0: Undefined
1: Acknowledged
2: Unacknowledged
-
Update State
D-R
1
0: Undefined
1: Update reported
2: Update not reported
-
Time Stamp
D-R
8
-
Static Revision D-R
2
0 ≤ X ≤ 65535
-
Relative Index D-R
2
0 ≤ X ≤ 65535
-
36
BLOCK_ALM
Parameter for generating an alert when
fixed data (data whose access attribute is
“S-”) of the Resource block is changed. The
configuration is as follows:
· Unacknowledged: Determined state
· Update_State: Change state
· Time_stamp: Change time
· Static_Revision: Revision after change
· Relative_Index: Changed parameter
identification number
Unacknowledged D-R/W
1
0: Undefined
1: Acknowledged
2: Unacknowledged
-
Alarm State
D-R
1
0: Undefined
1: Clear - reported
2: Clear - not reported
3: Active - reported4
: Active - not reported
-
Time Stamp
D-R
8
-
Subcode
D-R
2
-
Value
D-R
1
-
37
ALARM_SUM
Parameter that indicates the state of
BLOCK_ALM of the Resource block
comprehensively. The configuration is as
follows:
· Current: Current generation state
· Unacknowledged: Alarm checking state
· Unreported: Reporting state to the host
devices
· Disabled: Alarm detection inhibit state
Current
D-R
2
bit1: High high alarm
-
Unacknowledged D-R
2
bit5: Deviation high alarm
-
Unreported
D-R
2
bit6: Deviation low alarm
-
Disabled
S-R/W
2
bit7: Block alarm
0
Summary of Contents for MagneW Plus+ MGG14C
Page 6: ...iv ...
Page 8: ...vi ...
Page 11: ...1 3 Figure1 3 System using a Foundation Fieldbus ...
Page 14: ...1 6 The following table is a summary of the functions of each of the keys ...
Page 26: ...2 6 ...
Page 42: ...4 6 ...
Page 78: ...A 10 ...
Page 105: ......
Page 108: ......
Page 110: ......