AB-7050 

10 

Installation 

 CAUTION 

 

Use the product under the operating conditions (temperature, humidity, power, vibration, shock, mounting direction, 
atmospheric condition, etc.) as listed in the specifications.  
Failure to do so might cause fire or device failure. 

 

Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.

 

Requirements for installation location 

IMPORTANT: 

  Installation location of Neosensor largely affects temperature/humidity control.  Carefully select the location. 

  Chemical (organic solvent) atmosphere may shift the output values. 

  Corrosive gas, organic solvent, and other chemicals contained in the atmosphere can cause measuring error 

of Neosensor, shorten the service life of Neosensor, or damage Neosensor. 
Ask our salesperson for use of Neosensor in a special application, as mentioned above. 

 

Install Neosensor on an indoor wall where: 

  Representative temperature and humidity (of the room/zone to control) are measured (approx. 1.5 m high above the floor). 

  Ambient air velocity is 0.1 to 0.15 m/s. 

  There is enough maintenance space left in front of Neosensor. 

Do not install Neosensor on a wall where: 

  Heat (generated by office device or equipment, for example) stays on. 

  Air circulation is interfered (by furniture or door, for example). 

  Temperature and/or humidity sensing is affected by draft, downdraft, and hot/cold air from water pipes/ducts. 

  Temperature and/or humidity sensing is affected by weather conditions (including sunlight and outdoor air). 

  There is vibration. 

  Dew condensation occurs. 

 Water 

drops. 

  Corrosive gas, organic solvent, or other chemicals is contained in the atmosphere. 

Do not install Neosensor outdoors or in a duct. 

Do not horizontally install Neosensor directly on a ceiling surface. 

 

Precautions for installation 

  Install Neosensor with a dedicated mounting kit (sold separately) suitable for your application. 

  Do not allow any refuse such as an electric wire scrap to get inside Neosensor. 

  Do not get a cable caught between the Neosensor main unit and the mounting surface. 

  Carefully handle Neosensor when the cover is removed so that the element does not get damaged. 

  Check that the ambient air velocity is sufficient in a location (not on a ceiling surface) where Neosensor will be horizontally 

installed. 

  If air infiltrates to the rear side of the Neosensor from the inside of the installed wall through the outlet box, shut off the air by 

sealing the outlet box. 

  After installation, leave Neosensor well so that it adapts to ambient conditions (atmospheric environment). 

 

Summary of Contents for HTY7043T1P00

Page 1: ...sing Neosensor is thus suitable for various applications such as commercial building air conditioning or other indoor uses Note The specification data of the two wire 4 20mA output model of Neosensor...

Page 2: ...bligatory action to prevent possible danger The symbol inside graphically indicates the actual action to be carried out For example the sign on the left indicates general instructions CAUTION Use the...

Page 3: ...ow Available model numbers Model number Type Power Humidity output Temperature output Signal output wire connection Company logo HTY7043T1P00 Yes HTY7043T1P00 1 Neosensor 24 V DC AC 1 5 VDC RTD Pt100...

Page 4: ...iring Thermoplate for open wiring is used for open wiring installation Part No DY2000A3021 For mounting three Neosensor crosswise Auxiliary device Multi Thermocase Model TY1100Z LAN cable Part No DY72...

Page 5: ...tion resistance Min 500 V DC 20 M Withstand voltage 500 V AC applied for 1 min with max of 1 mA leakage current between housing and terminals Environmental conditions Rated operating condition Limit o...

Page 6: ...tead of lead wires Model TY7043Z0P01 1 Figure 1 Mounting dimensions mm Neosensor with Wall direct mounting kit Neosensor high sensitive type Note For wiring secure more than 15 mm clearance inside the...

Page 7: ...unting surface when installing Neosensor with Thermoplate mounting kit 2 The number of lead wires differs depending on the models Note that the Pt100 temperature sensor model with modular connection h...

Page 8: ...th Thermoplate mounting kit Figure 5 Mounting dimensions mm Neosensor high sensitive type with Thermoplate mounting kit on Thermoplate Thermoplate mounting kit Figure 6 Dimensions mm Mounting plate of...

Page 9: ...sensor model with modular connection has a modular jack instead of lead wires Model TY7043Z0P01 1 Figure 7 Mounting dimensions mm Neosensor not covered with Multi Thermocase mounting kit Multi Thermoc...

Page 10: ...rated by office device or equipment for example stays on Air circulation is interfered by furniture or door for example Temperature and or humidity sensing is affected by draft downdraft and hot cold...

Page 11: ...14 5 Set the depth change levers on the bilateral sides of the Neosensor main unit to the upper position indicated with L shown in Fig 17 6 Mount the main unit of Neosensor on the main unit of the Wa...

Page 12: ...d with L shown in Fig 17 6 Mount the main unit of Neosensor on the main unit of the Wall direct mounting kit with four mounting screws M3 16 supplied with Neosensor 7 Attach the cover back to the Neos...

Page 13: ...on the bilateral sides of the Neosensor main unit to the upper position indicated with L shown in Fig 17 7 Mount the main unit of Neosensor on the main unit of the Thermoplate mounting kit with four...

Page 14: ...lled with its cover removed IMPORTANT Before installing Neosensor in the Multi Thermocase be sure to set the depth change levers on the bilateral sides of the Neosensor main unit at the lower position...

Page 15: ...pth change Raising the Neosensor main unit 3 Set the depth change levers located on the bilateral sides on the main unit front surface at the lower position The levers are factory set at the upper pos...

Page 16: ...ck Blue Black 24 V AC DC 1 5 V DC 0 10 V DC Power supply Humidity Models HY7043T1000 1 and HY7043T6000 1 Figure 22 Terminal wiring Humidity sensor with 1 5V 0 10V humidity output 24 V AC DC power Pt10...

Page 17: ...sor temperature humidity sensor models IMPORTANT Use isolated transformer to supply 24 V AC power Single Neosensor must be powered by a single 24 V AC transformer If the multiple Neosensor or a Neosen...

Page 18: ...wing Use a controller with low pass filter 40 dB or higher removal ratio in normal mode that receives signals from Neosensor For insufficient removal ratio provide an isolator on the controller input...

Page 19: ...ration Neosensor is factory calibrated and does not require field calibration right after installation However field calibrate Neosensor if a shift in the output due to aged deterioration is found For...

Page 20: ...ademark of Azbil Corporation in Japan or in other countries Specifications are subject to change without notice Building Systems Company http www azbil com Rev 2 0 Sep 2015 AB 7050 J AI 7050 Rev 3 2 P...

Reviews: