4-64
Chapter 4. Functions
z
Event main setting, event subsetting, hysteresis, delay
The event main setting, event subsetting, hysteresis, and ON and OFF delays
associated with the event operation type can be set.
A total of 16 events is available for loops 1 to 4.
Item (bank)
Display
Description
Initial value
Direct/reverse
(Event configuration bank)
MENU > EventConfig
Direct/reverse
0: Direct
1: Reverse
0
Standby
(Event configuration bank)
MENU > EventConfig
Standby
0: No
1: Standby
2: S standby when the SP is modified
0
READY mode operation
MENU > EventConfig
READY mode operation
0: Continue
1: Force OFF
0
ON delay time
(Event configuration bank)
MENU > EventConfig
ON delay
0.0000 to 3200.0 s
0.0000
OFF delay time
(Event configuration bank)
MENU > EventConfig
OFF delay
0.0000 to 3200.0 s
0.0000