Table 3  Inspection items and inspection method

Item

Inspection 

cycle

Inspection method

Visual check

6 months

• There is no leakage from the grand and flange.
• Loose bolts.
• There is no damage on the valve and actuator.

Operation status

6 months

• The valve is smoothly opened or closed.
• Check that no abnormal sound or vibration is observed.

Daily inspection

W h e n e v e r 

necessary

• Check that there is no leakage of fluid to the outside of the valve.
• Check that no abnormal sound or vibration is observed.
• The valve is smoothly opened or closed.
• Check that there is no hunting observed with the valve.

Table 4  Troubleshooting

Abnormal phenomenon

Where to inspect

Measure

Leakage from the flange

Loose flange bolts

Gasket on the flange. Misaligned pipes

Retighten the flange bolts.

Replace the gasket. Do piping again.

Leakage from the gland

ーーーーー

Contact Azbil Corporation

Leakage from the top lid joint.

Loose bolts

Retighten the bolts.

The valve is not smoothly opened 

or closed.

The valve stops halfway.

The valve does not move.

Check that the power line and the input 

signal are correctly fed.

Loose terminals

Check that wires are firmly connected, 

no disconnected wire.

Check the power supply voltage and 

the controller.

Retighten the terminals.

Check the wirings.

Leakage is observed when the 

valve is fully closed.

Pointer position when the valve is fully 

closed

Fully close the valve.

Abnormal sound or vibration is 

observed.

Check that level of pressure at the pri-

mary is adequate. Check the level of 

differential pressure.

Adjust the mounting conditions.

The auxiliary switch does not 

work.

Check the conditions of the auxiliary 

switch cam.

Loose terminals

Check that wires are firmly connected, 

no disconnected wire.

Do settings again.

Retighten the terminals.

Check the wirings.

The auxiliary potentiometer does 

not work.

Resistance value

Loose terminals

Check that wires are firmly connected, 

no disconnected wire.

Check the resistance.  (1k

Ω

)

Retighten the terminals.

Check the wirings.

Valve hunting

Level of pressure and differential pres-

sure at the secondary

Stability of control

Adjust the mounting conditions.

Adjust the settings of control parame-

ter such as PI.

Mismatch between the input sig-

nal and the feedback signal in 

the voltage/current input specifi-

cations

ーーーーー

If the input specification is voltage or 

current, the valve moves from 0 % to 

100 % corresponding to the input sig-

nal from 10 % to 90 % in order to fully 

close the valve.

Therefore, the input signal and the 

feedback signal do not match, but it is 

not abnormal.

 

„

Disposal

Dispose of this product as industrial waste in accordance with your local regulations. 
Do not reuse all or any part of the product.

Summary of Contents for ACTIVAL SCS13A

Page 1: ...mostat Model TY9800 4 20 mA DC input Provides proportional control in combination with a DDC controller e g Infilex GC Model WY5111 Model R35 R36 2 10 V DC input Provides proportional control in combi...

Page 2: ...equency of use as basic parameters The recommended design life of this product is 10 years The recommended design life assumes that maintenance such as replacement of the limited life parts is carried...

Page 3: ...125 CAUTION After installation make sure no fluid leaks from the valve pipe connections Improper piping may cause fluid leakage outside of the valve Do not put a load or weight on this product Doing s...

Page 4: ...ers 1 Total resistance Nominal 1 k Operation range 0 fully closed to 100 fully open Max applied voltage 5 V DC Note It cannot be connected with Model M904E Valve flange adapter kit 4 Valve size Major...

Page 5: ...on location Indoor use Note Salt air corrosive gas flammable gas and organic solvent must be avoided Outdoor use Note Salt air corrosive gas flammable gas and organic solvent must be avoided And use t...

Page 6: ...mperature of fluid Chilled hot water 0 175 C Note When using the stainless steel valve with chilled water of 0 C or lower please contact Azbil Corporation 175 C steam 0 175 C 200 C steam 0 200 C Flow...

Page 7: ...tion applied for the 4 20 mA DC input and 2 10 V DC input Output voltage range 2 V DC fully closed to 10 V DC fully open Maximum load resistance 10 k or more max output current 1 mA Valve position Ind...

Page 8: ...maintenance 2 For setting the auxiliary switch make sure to allow a clearance of 300 mm or more Figuar 1 Dimensions mm Table 1 Dimension table mm Valve size L L1 H H1 D C t h N DN15 108 50 213 75 95 7...

Page 9: ...For setting the auxiliary switch make sure to allow a clearance of 300 mm or more Figuar 2 Dimensions mm Table 2 Dimension table mm Valve size L L1 H H1 D C g t h N DN15 108 50 213 75 95 70 51 12 15 4...

Page 10: ...AB 6464 10 Parts Indication Actuator Yoke Valve body Pointer Terminal cover Top cover Knockout hole Top lid Top cover Joint Stem Gland packing Seat ring Plug Figuar 3 Parts Indication...

Page 11: ...ve install it on the pipe diverting sections for each piping group Do not install this product near a steam coil hot water coil etc High temperature radiant heat may cause failure of the actuator Avoi...

Page 12: ...he factory CAUTION After installation make sure no fluid leaks from the valve pipe connections Improper piping may cause fluid leakage outside of the valve Do not put a load or weight on this product...

Page 13: ...te A special sheet is inserted between the yoke and valve for heat insulation When you changed the mounting position be careful not to lose the sheet 4 Make sure that the groove on the tip of the valv...

Page 14: ...y of the power supply and 2 10 V DC feedback signal and then correctly wire the product Incorrect wiring may result in PCB print circuit board burnout z z How to maintain IP54 dust proof splash proof...

Page 15: ...terminals 4 to 7 Note Correctly connect the wires referring to Fig 9 to Fig 13 Terminals Connection Fig 14 to Fig 27 Wiring Examples and Advanced Wiring Examples 4 Mount the terminal cover and attach...

Page 16: ...troller V Voltage between 4 and 6 Figuar 10 z z Nominal 135 resistance input Model VY512_J 4 5 6 7 To controller 24 V AC power Open Open R B W T2 T1 1 3 2 Figuar 11 z z 4 20 mA DC input Model VY513_J...

Page 17: ...put Model VY513_ Model R35 Model R36 ACTIVAL 4 20 mA DC input Model VY513_ 4 5 6 7 T1 T2 1 2 1 3 2 Power transformer Model AT72 J1 100 200 V AC 1 The terminal 2 power terminal 5 4 20 mA DC input and t...

Page 18: ...ce life the minimum opening position cannot be maintained Avoid instrumentation that may cause secondary dam age in case of abnormality Figuar 18 Using relay interlock ACTIVAL Nominal 135 resistance i...

Page 19: ...duct will malfunction Input signals and power are shared Model R35TC0 Model R36TC0 ACTIVAL 4 20 mA DC input Model VY513_ Isolator 2 3 3 1 1 2 3 4 5 6 7 ACTIVAL 4 20 mA DC input Model VY513_ Isolator m...

Page 20: ...ed 2 Terminals 2 5 and 7 are internally connected 3 Refer to notes under Power transformer is shared Figuar 24 Power is shared Model WY5117 Model WY5117 ACTIVAL 2 10 V DC input Model VY514_ Isolator 2...

Page 21: ...ON Do not put a load or weight on this product Doing so may damage the product Before doing maintenance be sure to turn off the power to this product Failure to do so may result in electric shock or d...

Page 22: ...rminals Check the wirings Leakage is observed when the valve is fully closed Pointer position when the valve is fully closed Fully close the valve Abnormal sound or vibration is observed Check that le...

Page 23: ...AB 6464 23 This blank page was added for page layout purposes...

Page 24: ...al and Electronic Equipment Directive RoHSD EMCD EN 61000 6 2 EN 55011 Class A Group 1 RoHSD EN 50581 ACTIVAL is a trademark of Azbil Corporation Infilex is a trademark of Azbil Corporation Specificat...

Reviews: